🚧 Under construction — VoTechWorks is being built. A free tech program — complimentary, as our commitment to get America working.
voTechWorksGrade 13 · a vocational technology learning center, by urbanicity
newSchoolWorks.com › VoTechWorks › Building & Construction › HVAC/R › Heat Pumps: Principles, Installation, and Service › Lesson 2
BLD-HVAC07-04 · Lesson 2 · 14 clock hours · demo

The Reversing Valve: Operation, Wiring, and Common Failures

Objective. The student will describe how a four-way reversing valve shifts refrigerant flow and demonstrate how to test the valve solenoid coil and pilot tube operation using a multimeter and manifold gauge set.

How the Four-Way Reversing Valve Works

A heat pump moves heat in two directions — into the building for heating and out of the building for cooling — using the same refrigerant circuit. The four-way reversing valve makes that direction change possible. It is a slide-type valve with four pipe connections: the discharge line from the compressor (high-pressure vapor), the suction line back to the compressor (low-pressure vapor), and two lines that connect to the outdoor coil and the indoor coil. By shifting a sliding spool inside the valve body, the refrigerant path is rerouted so that which coil acts as condenser and which acts as evaporator is swapped.

The valve body contains a main slide (sometimes called the shuttle or piston) and a small pilot valve controlled by an electromagnet — the solenoid coil. When the solenoid coil is de-energized, spring pressure holds the pilot valve in one position, directing high-pressure gas to one end of the main slide and low pressure to the other. The pressure difference pushes the slide to one end of the body. When the solenoid coil is energized, it pulls the pilot valve to the opposite position, reversing which end of the main slide sees high pressure, and the slide shifts to the other end.

Most residential heat pumps energize the solenoid in cooling mode and de-energize it in heating mode, but this varies by manufacturer — always check the unit's wiring diagram before diagnosing.

The Pilot Tubes

Three small capillary tubes (pilot tubes) connect the pilot valve section to the ends of the main slide cylinder and to the discharge port. These tubes carry the pressure signals that move the main slide. A blocked or kinked pilot tube prevents the main slide from shifting even if the solenoid coil works perfectly. This is one of the most common causes of a valve that appears to be stuck.

Wiring the Solenoid Coil

The solenoid coil receives its signal from the thermostat control board — typically through the O terminal (some manufacturers use B). When the thermostat calls for a mode change, it energizes or de-energizes the O/B terminal, which in turn energizes or de-energizes the coil. The coil is a simple electromagnet: a coil of wire wound around a hollow bobbin that slides over the valve stem. Coils are field-replaceable without reclaiming the refrigerant charge — only the coil is changed, not the valve body.

Common coil voltages are 24 V AC (most residential controls) and 240 V AC (some commercial units). Always confirm supply voltage before touching wiring.

Safety Before You Start

Testing the Solenoid Coil with a Multimeter

A failed solenoid coil is one of the three most common reversing valve problems. Use a digital multimeter set to the ohms (Ω) function to test the coil.

1. De-energize the unit and apply lockout/tagout.

2. Disconnect the coil leads from the control circuit.

3. Measure resistance across the two coil terminals.

4. Compare to specification. Manufacturer service bulletins list the acceptable resistance range for each coil model. A reading of OL (open loop / infinite resistance) means the coil winding is broken — replace the coil. A reading of zero or near-zero ohms indicates a shorted coil — replace the coil. A reading within the published range means the coil is likely serviceable.

You can also perform a voltage check at the coil terminals with the unit energized in the correct mode to confirm the control board is delivering the signal — but only do this if LOTO is not practical at that step, using full PPE and keeping clear of live terminals.

Using Manifold Gauges to Confirm Valve Shifting

Once the electrical side checks out, confirm mechanically that the slide is moving:

1. Connect manifold gauges to the system's service ports.

2. Start the unit in one mode (e.g., cooling) and note suction and discharge pressures.

3. Command a mode change at the thermostat and observe the gauges. Within a few seconds, suction and discharge pressures should redistribute — the former high-side coil drops in pressure and the former low-side coil rises.

4. If pressures do not redistribute, the slide has not shifted. Check pilot tubes for blockage and listen for the faint "click" or "whoosh" of the slide moving.

Three Common Failure Modes

| Failure | Likely Cause | Diagnostic Clue | Typical Repair |

|---|---|---|---|

| Stuck slide | Contamination, worn slide, blocked pilot tube | Pressures do not equalize between modes; coil resistance OK | Clear pilot tube or replace valve |

| Leaking slide | Worn slide seal | High superheat on suction; unit short-cycles; pressures equalize slowly | Replace valve |

| Failed solenoid coil | Open or shorted winding | OL or 0 Ω on multimeter; no audible click | Replace coil only |

A leaking slide allows high-pressure discharge gas to bypass into the suction side continuously; this raises suction pressure and lowers system capacity. It is confirmed by suction pressure being higher than expected for the operating conditions and by comparing actual superheat to expected superheat.

Key Points to Remember

Key terms9

Four-way reversing valveA refrigerant valve with four pipe connections that redirects refrigerant flow to switch a heat pump between heating and cooling modes.
Solenoid coilAn electromagnet wound around a bobbin that, when energized, moves the pilot valve inside the reversing valve to initiate a slide shift.
Pilot valveA small internal valve controlled by the solenoid coil that routes high- and low-pressure signals to move the main slide.
Pilot tubesSmall capillary tubes connecting the pilot valve to the ends of the main slide cylinder; they carry the pressure signals that physically shift the slide.
Main slide (shuttle)The moving internal piston inside the reversing valve body that physically redirects refrigerant flow between the indoor and outdoor coils.
O terminal / B terminalThermostat control board terminals used to energize or de-energize the reversing valve solenoid coil; O energizes in cooling on most brands, B energizes in heating on some brands.
Leaking slideA worn or damaged main slide that allows high-pressure discharge gas to bypass directly into the suction side, reducing system capacity.
Coil resistance specificationThe manufacturer-published ohm range for a serviceable solenoid coil; readings outside this range (OL or near zero) indicate coil failure.
Lockout/tagout (LOTO)An OSHA-required safety procedure that physically locks a disconnect in the off position and tags it to prevent unexpected re-energization during service.

Worked examples4

1. A digital multimeter reads 48 Ω across a 24 V AC reversing valve solenoid coil. The manufacturer's service bulletin states the acceptable resistance range is 40–60 Ω. Is the coil serviceable?
  1. Identify the measured value: 48 Ω.
  2. Identify the manufacturer's specification range: 40–60 Ω.
  3. Compare: 40 Ω ≤ 48 Ω ≤ 60 Ω — the reading falls within the acceptable range.
Answer: Yes, the coil is serviceable. The 48 Ω reading is within the 40–60 Ω specification. Look elsewhere for the fault.
2. The multimeter reads OL (over-limit / infinite resistance) across the same solenoid coil terminals. What does this indicate and what is the correct action?
  1. OL means the circuit is open — current cannot flow through the coil winding.
  2. An open winding means the coil cannot create a magnetic field, so the pilot valve will not move regardless of the control signal.
  3. Confirm by re-measuring in case of a loose probe connection; if OL persists, the coil has failed.
Answer: The coil winding is broken (open circuit). Replace the solenoid coil. The valve body does not need to be replaced; the coil slides off the valve stem and a new coil slides on.
3. A technician measures 1 Ω across the solenoid coil terminals. The specification range is 40–60 Ω. What is the diagnosis?
  1. Measured value: 1 Ω.
  2. Specification range: 40–60 Ω.
  3. 1 Ω is far below the minimum of 40 Ω, indicating a shorted coil winding where turns of wire are contacting each other, drastically reducing resistance.
  4. A shorted coil may draw excessive current, blow a fuse, or fail to produce sufficient magnetic force.
Answer: The coil is shorted and has failed. Replace the solenoid coil and inspect the control circuit fuse before restarting the system.
4. After commanding a mode change at the thermostat, suction pressure on the manifold gauge does not change from 70 psig and discharge remains at 260 psig after 30 seconds. Coil resistance checked at 52 Ω (spec: 40–60 Ω) and 24 V AC is confirmed at the coil terminals. What is the most likely cause?
  1. The coil resistance is within spec and the correct voltage is present — the electrical side is working.
  2. The slide has not shifted despite the electrical signal being correct.
  3. Possible mechanical causes: blocked pilot tube, stuck or contaminated main slide.
  4. Inspect pilot tubes for kinks or blockage; tap the valve body gently with a rubber mallet (unit running) to free a stuck slide — if the slide then moves, the valve is worn and should be replaced.
Answer: The most likely cause is a blocked pilot tube or a mechanically stuck main slide. The electrical system is functioning correctly. Further mechanical inspection of the pilot tubes and slide is required.
In class: Instructor demonstrates reversing valve operation on a cut-away valve mounted on a display board, energizing and de-energizing the solenoid coil while students observe the slide shifting and record inlet/outlet pressure changes. · Students measure solenoid coil resistance with a digital multimeter, compare reading to manufacturer specification range, and determine whether the coil is serviceable or failed. · Complete a troubleshooting decision tree worksheet covering three scenarios: stuck slide, leaking slide, and failed solenoid coil; identify the correct diagnostic steps and repair actions for each.
Materials: Cut-away reversing valve display board, Ranco or Sporlan reversing valve service bulletin, digital multimeter, manifold gauge set, manufacturer wiring diagram, troubleshooting worksheet
Check: Instructor observation checklist: student correctly measures coil resistance and interprets result; correctly traces the valve position on a wiring diagram; pass mark 80% of checklist items.

Practice check8

Answer each question, then check it. Nothing is recorded; this is your own practice.

Heat pump systems — refrigerant flow and controls
1. In most residential heat pumps, the reversing valve solenoid coil is energized during which operating mode?
Electrical diagnosis — NATE core and HVAC Excellence
2. A technician measures the solenoid coil resistance and the multimeter displays OL. What is the correct interpretation?
Heat pump systems — component identification
3. Which component physically redirects refrigerant flow inside the four-way reversing valve body?
Heat pump troubleshooting — NATE heat pump specialty
4. A heat pump is stuck in cooling mode. The solenoid coil resistance is within specification and the correct control voltage is present at the coil terminals. Manifold gauges show pressures do not redistribute after a mode-change command. Which of the following is the most likely cause?
Safety — EPA 608 and NCCER safety practices
5. Which safety procedure must be applied to a heat pump's disconnect before a technician disconnects solenoid coil wiring for resistance testing?
Heat pump troubleshooting — refrigerant system analysis
6. A reversing valve with a leaking main slide will most likely cause which symptom?
Heat pump service procedures — HVAC Excellence and NATE
7. When replacing a failed solenoid coil on a reversing valve, which statement is correct?
Heat pump diagnosis — manifold gauge use and system analysis
8. When connecting manifold gauges to confirm reversing valve operation, which observation confirms that the main slide has successfully shifted to a new position?
Record this lesson on my transcript. Sign in with your key and enrollment email to record lessons (enroll free if you have no key). This page stays open to read and practise.