newSchoolWorks.com › VoTechWorks › Building & Construction › Electrical › Motors & Controls › Lesson 4
BLD-ELEC05-06 · Lesson 4 · 18.5 clock hours · theory

Schematic and Wiring Diagram Reading

Objective. Students trace current flow through ladder-logic schematic diagrams and translate them into wiring diagrams for two-wire and three-wire motor control circuits.

Why Two Types of Diagrams?

Electricians use two complementary drawings to design, install, and troubleshoot motor control circuits. A schematic (ladder) diagram shows how the circuit works — the logic of control. A wiring diagram shows how to connect the physical hardware — terminal to terminal. You must be comfortable moving between both.

The Ladder Schematic

A ladder diagram gets its name from its shape. Two vertical lines called power rails run down the page. The left rail carries the control voltage (often labeled L1); the right rail is the neutral or return side (often labeled L2). Horizontal lines called rungs stretch between the rails. Each rung is one control circuit: contacts on the left side of the rung switch current to a load (coil, pilot light, or relay) on the right side.

Rungs are numbered from top to bottom. Contacts are labeled with the device designation that operates them — for example, M1 means a contact controlled by the M1 motor contactor coil. You always read a ladder diagram left to right and top to bottom, tracing current from L1 through any closed contacts to the load and back to L2.

Contact and Coil Symbols

Always note the normal state: "normal" means the device is at rest, with no power applied and no mechanical force acting on it.

Two-Wire Control (Maintained Contact)

A two-wire circuit uses a single maintained-contact device — a thermostat, float switch, or toggle switch — wired directly in series with the contactor coil. When the contact closes, the coil energizes and the motor runs. When it opens, the motor stops. There is no separate stop button and no holding contact. This circuit allows automatic restart after a power failure, which can be a hazard if workers are near the machine. Verify with your supervisor whether automatic restart is acceptable for a given installation.

Three-Wire Control (Momentary Start-Stop with Holding Contact)

The three-wire circuit uses a momentary normally open START button, a momentary normally closed STOP button, and a set of auxiliary (holding) contacts on the contactor itself. Here is the logic:

1. Pressing START closes the NO contact momentarily → coil M1 energizes → motor starts.

2. Simultaneously, the M1 auxiliary NO contact (wired in parallel with the START button) closes → this seals in (holds) the circuit so the coil stays energized after you release START.

3. Pressing STOP opens the NC contact → coil de-energizes → motor stops → M1 auxiliary contact opens → circuit resets.

Because the seal-in contact drops out on a power failure, the motor will not restart automatically when power returns. This is the safer default for most industrial and commercial motor installations and is required by code in many applications.

Reversing Starter Circuits

A reversing starter uses two contactors — Forward (F) and Reverse (R). Swapping any two motor leads (typically T1 and T3) reverses rotation. The ladder schematic must include electrical interlocks: a NC contact of F in the R rung, and a NC contact of R in the F rung. This prevents both contactors from closing at the same time, which would create a line-to-line short circuit. Many reversing starters also include mechanical interlocks built into the contactor assembly. Never rely on software or operator habit alone — always wire both interlocks.

From Schematic to Wiring Diagram

A point-to-point wiring diagram shows the actual terminals on each device and the wire run between them. To translate:

1. Identify every device in the schematic (contactor, push-button station, overload relay).

2. Look up terminal designations in the manufacturer's catalog (for example, A1/A2 for the coil, 13/14 for an auxiliary NO contact).

3. Draw each device as a box labeled with its terminal numbers.

4. Draw a line for each wire, annotating with wire number or color.

5. Verify polarity: L1 must not connect to L2 through any path that bypasses a load.

Double-check every connection before energizing. A crossed-polarity or missing connection in a motor control circuit can destroy equipment and injure workers.

Safety Points

Key terms10

Ladder (schematic) diagramA control circuit drawing arranged like a ladder, with two vertical power rails and horizontal rungs showing the logical sequence of contacts and loads.
Wiring (point-to-point) diagramA drawing that shows the physical terminals on each device and the actual wire connections between them, used to install or troubleshoot hardware.
Normally Open (NO) contactA contact that is open (non-conducting) when the controlling device is in its de-energized or rest state; it closes when the device is activated.
Normally Closed (NC) contactA contact that is closed (conducting) when the controlling device is in its de-energized or rest state; it opens when the device is activated.
Seal-in (holding) contactAn auxiliary NO contact on a contactor wired in parallel with the START button; it closes when the coil energizes, maintaining the circuit after the START button is released.
Two-wire controlA motor control scheme using a single maintained-contact device in series with the coil; the motor restarts automatically after a power interruption.
Three-wire controlA motor control scheme using a momentary START button, a momentary STOP button, and a seal-in contact; the motor does not restart automatically after a power loss.
Electrical interlockA normally closed auxiliary contact of one contactor wired into the control rung of a second contactor to prevent both from energizing simultaneously.
Power railEither of the two vertical lines in a ladder diagram representing the supply (L1) and return (L2) sides of the control voltage source.
Contactor coilThe electromagnetic winding inside a contactor; when energized it closes the main power contacts and any auxiliary contacts associated with that device.
In class: Lecture on diagram conventions: power rail numbering, contact symbols (NO, NC), coil symbols, and the difference between schematic (ladder) and wiring diagrams; students copy key symbols into a personal reference card. · Diagram tracing exercise: students use colored pencils to trace energized and de-energized current paths through a printed two-wire (maintained contact) and a three-wire (momentary start-stop with holding contact) circuit. · Translation task: students receive a ladder schematic for a reversing starter and redraw it as a point-to-point wiring diagram showing terminal numbers on a contactor and push-button station.
Materials: Printed schematic packets; NCCER Electrical Level 2 motor controls module; colored pencils; blank wiring diagram templates; Allen-Bradley or similar catalog for contactor terminal identification
Check: Diagram translation reviewed by instructor; student must correctly identify all current paths and produce a wiring diagram with no crossed-polarity or missing connections (100% accuracy on safety-critical connections; 80% overall).

Practice check8

Answer each question, then check it. Nothing is recorded; this is your own practice.

NCCER Electrical L2 – Motor Controls
1. In a ladder diagram, the two vertical lines on the left and right sides of the drawing are called:
NCCER Electrical L2 – Motor Controls
2. A normally open (NO) contact symbol indicates that the contact is in what state when the controlling device is de-energized?
NCCER Electrical L2 – Motor Controls
3. Which circuit type allows a motor to restart automatically after a power failure?
NCCER Electrical L2 – Motor Controls
4. In a three-wire control circuit, what is the purpose of the auxiliary contact wired in parallel with the START button?
NCCER Electrical L2 – Motor Controls
5. In a reversing motor starter, the electrical interlock consists of:
NCCER Electrical L2 – Motor Controls
6. When translating a ladder schematic into a point-to-point wiring diagram, which information must you obtain from the manufacturer's catalog?
OSHA 10 – Electrical Safety / Hazardous Energy Control
7. Before opening a motor control panel to trace wiring, an electrician must first:
NCCER Electrical L2 – Motor Controls
8. A student traces a ladder diagram and finds two separate current paths that both lead from L1 to L2 without passing through any load device. This most likely indicates: