BLD-SOLA09-07 · Lesson 2 · 14 clock hours · theory
PV Source and Output Circuits: Voltage, Current, and Conductor Sizing
Objective. Students will apply NEC 690.8 and the applicable conductor ampacity tables to calculate the minimum conductor size and overcurrent device rating for a given PV source circuit and PV output circuit.
⚠ Pending professional review
This lesson, its worked examples and its practice questions has not yet been verified by a licensed professional engineer or master tradesperson or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.
VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.
Why Conductor Sizing in PV Systems Demands Special Attention
Photovoltaic source and output circuits behave differently from ordinary branch circuits. A PV array produces current whenever sunlight falls on it — you cannot simply open a breaker upstream and expect current to stop, the way you can with a utility feed. That characteristic makes correct conductor sizing and overcurrent protection critical for fire prevention and installer safety. NEC Article 690 addresses these unique properties directly, and Section 690.8 is the calculation engine every installer uses.
Circuit Definitions You Must Know
Before calculating anything, you need to know which circuit you are sizing.
PV source circuit: the conductors from the modules or a series string of modules up to the combiner box (or the first overcurrent device). Each string is a source circuit.
PV output circuit: the conductors from the combiner box (or parallel connection point) to the inverter. This circuit carries the combined current of all parallel strings.
The distinction matters because the current values differ: a source circuit carries one string's current; an output circuit carries the sum of all strings.
The NEC 690.8 Calculation Sequence
NEC 690.8 establishes two separate multiplier paths — one for conductor ampacity and one for overcurrent device rating.
Step 1 — Determine the Maximum Circuit Current
For a source circuit or output circuit, the maximum circuit current is based on the module's short-circuit current (Isc) as listed on the module nameplate or specification sheet.
For a single string (source circuit): maximum current = Isc of one module (all modules in series carry the same current).
For multiple parallel strings (output circuit): maximum current = Isc × number of parallel strings.
Step 2 — Apply the 690.8 Multiplier for Ampacity
NEC 690.8(A) states that PV system conductors must be sized to carry 125% (1.25×) of the maximum circuit current. This factor accounts for continuous operation in full sunlight conditions.
> Conductor ampacity requirement = Isc × 1.25
Step 3 — Apply the 690.8 Multiplier for Overcurrent Protection
NEC 690.8(B) states that the overcurrent protective device (OCPD) — fuse or breaker — rating must be at least 125% of the maximum circuit current. Because OCPDs are typically standard sizes, you round up to the next available standard rating after multiplying.
Some references describe this as a 1.25 × 1.25 sequence, meaning: first determine the 125% ampacity value from 690.8(A), then require the OCPD to also be rated at no less than that same 125% value. Both the conductor and the OCPD must independently satisfy 125% of Isc.
Step 4 — Apply Temperature and Conduit-Fill Correction Factors
After finding the minimum required ampacity from Step 2, you must derate the conductor's tabulated ampacity from NEC Table 310.16 for:
Ambient temperature: Use the correction factors in NEC Table 310.15(B)(1) (or the table header correction rows in 310.16). Higher ambient temperatures reduce a conductor's ability to dissipate heat.
Conduit fill (bundling): If more than three current-carrying conductors share a conduit or cable, use the adjustment factors in NEC Table 310.15(C)(1). More conductors in the same conduit means less heat dissipation per conductor.
Because derating reduces the conductor's effective ampacity, you may need to step up to a larger gauge than the 125% calculation alone would suggest.
Step 5 — Select the Conductor Gauge from NEC Table 310.16
NEC Table 310.16 lists the allowable ampacity of conductors by gauge (AWG or kcmil), insulation type, and temperature rating. For PV wiring in conduit, you will commonly use THWN-2 (90°C rated, wet location listed). After applying all correction factors, select the smallest standard conductor gauge whose corrected ampacity meets or exceeds the value from Step 2.
Rooftop Temperature Conditions — A Critical Safety Note
Modules mounted close to a roof can expose conduit and conductors to ambient temperatures well above the standard 30°C (86°F) baseline used in Table 310.16. Always check the installation conditions and apply the appropriate temperature correction factor. Undersized conductors in high-temperature rooftop locations are a leading cause of PV wiring failures and fires.
Safety Practices During and After Installation
Lockout/tagout (LOTO): PV conductors remain energized in daylight. Before working on any PV circuit, de-energize the inverter and the AC disconnect, but understand that the array-side DC conductors may still be live. Follow your employer's LOTO procedure and use a verified, properly rated DC voltage tester before touching conductors.
PPE: When measuring or connecting PV circuits, wear appropriately rated insulated gloves and safety glasses. DC arc flash is a serious hazard.
Insulation rating: Use only conductors and connectors rated for the system's maximum DC voltage and listed for PV use (USE-2 or PV Wire for exposed strings; THWN-2 in conduit).
Putting It All Together
The 690.8 sequence is straightforward if you work it in order: find Isc, multiply by 1.25 for the minimum conductor ampacity requirement, apply temperature and fill derating factors to the table values, then select a conductor gauge whose derated ampacity meets that requirement. The OCPD must also be rated at no less than 125% of Isc, rounded up to the next standard size. Accurate calculation protects the conductor from overheating, satisfies the AHJ inspector, and — most importantly — prevents fire.
Key terms10
Short-circuit current (Isc)The current a PV module or string produces when its output terminals are shorted; the highest current the module generates under standard test conditions and the baseline value used in NEC 690.8 calculations.
PV source circuitThe conductors connecting one series string of PV modules to the first overcurrent protective device or combiner box; carries the current of a single string.
PV output circuitThe conductors from the combiner box (or parallel connection point of multiple strings) to the inverter; carries the combined current of all parallel strings.
NEC 690.8The National Electrical Code section that establishes how to calculate maximum circuit current and sets the 125% multiplier requirements for PV conductor ampacity and overcurrent device ratings.
AmpacityThe maximum current, in amperes, that a conductor can carry continuously under specified conditions of use without exceeding its temperature rating.
Temperature correction factorA multiplier from NEC Table 310.15 applied to a conductor's tabulated ampacity to account for ambient temperatures above or below the baseline; reduces allowable ampacity as temperature rises.
Conduit-fill adjustment factorA multiplier from NEC Table 310.15(C)(1) applied when more than three current-carrying conductors share a raceway, reducing each conductor's allowable ampacity due to reduced heat dissipation.
Overcurrent protective device (OCPD)A fuse or circuit breaker that interrupts current when it exceeds the device's rating; in PV systems the OCPD rating must be at least 125% of the circuit's maximum current per NEC 690.8.
NEC Table 310.16The NEC table listing allowable ampacity for insulated conductors by wire gauge, insulation temperature rating, and number of conductors, used to select the correct conductor size after applying all derating factors.
Standard test conditions (STC)The controlled laboratory conditions (1000 W/m² irradiance, 25°C cell temperature, AM 1.5 spectrum) at which module electrical ratings, including Isc, are measured and published on the nameplate.
Worked examples4
1. Size the source circuit conductor and overcurrent device for a single string of modules with a nameplate Isc of 9.80 A. The string runs in conduit on a rooftop; assume ambient temperature correction factor of 0.87 (corresponding to the rooftop condition) and only three current-carrying conductors in the conduit (no bundling derating needed). Use THWN-2 conductors (90°C column of Table 310.16).
Step 1 — Maximum circuit current: single string, so maximum current = Isc = 9.80 A.
Step 2 — Minimum conductor ampacity per NEC 690.8(A): 9.80 A × 1.25 = 12.25 A. The conductor's derated ampacity must be at least 12.25 A.
Step 3 — Minimum OCPD rating per NEC 690.8(B): 9.80 A × 1.25 = 12.25 A. Round up to the next standard fuse or breaker size — 15 A.
Step 4 — Apply temperature correction to Table 310.16 values: divide the required ampacity by the correction factor to find the required tabulated ampacity: 12.25 A ÷ 0.87 = 14.08 A. The conductor chosen from Table 310.16 must have a tabulated ampacity of at least 14.08 A.
Step 5 — Select conductor from NEC Table 310.16 (90°C column, THWN-2): 14 AWG is rated 25 A, which exceeds 14.08 A. However, 14 AWG is protected by the 15 A OCPD, which is acceptable. Use 14 AWG THWN-2.
Answer: Minimum conductor: 14 AWG THWN-2. Minimum OCPD: 15 A (next standard size above 12.25 A).
2. An output circuit combines three parallel strings. Each module has an Isc of 10.20 A. The conductors run in conduit with no additional current-carrying conductors sharing the raceway. Ambient temperature correction factor is 0.91. Use THWN-2 (90°C column).
Step 1 — Maximum circuit current: 3 parallel strings × 10.20 A per string = 30.60 A.
Step 2 — Minimum conductor ampacity per NEC 690.8(A): 30.60 A × 1.25 = 38.25 A. Derated conductor ampacity must be ≥ 38.25 A.
Step 3 — Minimum OCPD rating per NEC 690.8(B): 30.60 A × 1.25 = 38.25 A. Round up to next standard size — 40 A.
Step 4 — Required tabulated ampacity before derating: 38.25 A ÷ 0.91 = 42.03 A. The Table 310.16 (90°C) value for the chosen conductor must be at least 42.03 A.
Step 5 — Select conductor: 8 AWG THWN-2 has a tabulated ampacity of 55 A in the 90°C column, which exceeds 42.03 A. Use 8 AWG THWN-2.
Answer: Minimum conductor: 8 AWG THWN-2. Minimum OCPD: 40 A.
3. Size the source circuit conductor for a single string where Isc = 8.60 A. The string conduit contains 6 current-carrying conductors (bundling adjustment factor from NEC Table 310.15(C)(1) = 0.80). Ambient temperature correction factor = 0.94. Use THWN-2.
Step 1 — Maximum circuit current: single string, maximum current = 8.60 A.
Step 2 — Minimum conductor ampacity per NEC 690.8(A): 8.60 A × 1.25 = 10.75 A.
Step 3 — Minimum OCPD rating: 8.60 A × 1.25 = 10.75 A; round up to 15 A (next standard size).
Step 5 — Required tabulated ampacity: 10.75 A ÷ 0.752 = 14.29 A. The Table 310.16 (90°C) value must be at least 14.29 A.
Step 6 — Select conductor: 14 AWG THWN-2 = 25 A tabulated (90°C), which exceeds 14.29 A. Use 14 AWG THWN-2.
Answer: Minimum conductor: 14 AWG THWN-2. Minimum OCPD: 15 A.
4. An output circuit combines 4 parallel strings; each module Isc = 9.50 A. Conduit has 4 current-carrying conductors (bundling factor = 0.80 per NEC Table 310.15(C)(1)). Ambient temperature correction factor = 0.87. Use THWN-2.
Step 1 — Maximum circuit current: 4 strings × 9.50 A = 38.00 A.
Step 2 — Minimum conductor ampacity per NEC 690.8(A): 38.00 A × 1.25 = 47.50 A.
Step 3 — Minimum OCPD rating: 38.00 A × 1.25 = 47.50 A; next standard size = 50 A.
Step 5 — Required tabulated ampacity: 47.50 A ÷ 0.696 = 68.25 A. Table 310.16 (90°C) value must be ≥ 68.25 A.
Step 6 — Select conductor: 6 AWG THWN-2 = 75 A (90°C column), which exceeds 68.25 A. Use 6 AWG THWN-2.
Answer: Minimum conductor: 6 AWG THWN-2. Minimum OCPD: 50 A.
In class: Instructor demonstration of the NEC 690.8 calculation sequence (Isc × 1.25 × 1.25 for overcurrent protection; Isc × 1.25 for ampacity) using a projected sample string datasheet, with students following along in their codebooks. · Worksheet problem set: each student works through six calculation scenarios (varying module Isc, number of parallel strings, conduit fill, and ambient temperature correction factors from NEC Table 310.15) and selects the correct wire gauge from NEC Table 310.16. · Peer-check round: partners swap worksheets, verify each calculation step using the codebook, and flag any deviation from the code-prescribed method before the instructor reviews answers as a class. Materials: NEC codebook, module spec sheets for three common 60-cell and 72-cell module types, NEC 690.8 calculation worksheet packet, scientific calculators, NEC Tables 310.15 and 310.16 laminated reference cards Check: Closed-book calculation quiz with four problems drawn from the worksheet set; students must show each multiplication step and cite the NEC table or section used; passing score 80 percent on each problem (all four required steps correct).
Practice check8
Answer each question, then check it. Nothing is recorded; this is your own practice.
NEC and Code Compliance
1. According to NEC 690.8, the minimum conductor ampacity for a PV source circuit is calculated by multiplying the module's short-circuit current (Isc) by which factor?
PV System Sizing and Design
2. A PV source circuit has a single string with a module Isc of 10.00 A. Ignoring derating factors, what is the minimum required conductor ampacity per NEC 690.8?
PV System Sizing and Design
3. A PV output circuit combines 4 parallel strings, each with an Isc of 9.00 A. What is the maximum circuit current used as the basis for NEC 690.8 calculations?
NEC and Code Compliance
4. After calculating the minimum required conductor ampacity for a PV source circuit, a designer finds that the conduit contains 6 current-carrying conductors. Which NEC resource provides the factor needed to adjust the conductor's tabulated ampacity for this condition?
PV System Sizing and Design
5. A source circuit conductor requires a derated ampacity of at least 14.50 A. After applying a temperature correction factor of 0.87 and a bundling factor of 0.80, what minimum tabulated ampacity must the conductor have in NEC Table 310.16?
System Design and Safety
6. Why must PV source circuit conductors be sized for continuous current conditions, unlike many conventional branch circuits?
Safety and Worker Protection
7. An installer is about to connect conductors at a rooftop combiner box during daylight. Which safety action is most critical before touching the DC conductors?
NEC and Code Compliance
8. After calculating that the minimum OCPD rating for a PV output circuit is 43.75 A, an installer checks the available standard fuse sizes (15, 20, 25, 30, 35, 40, 45, 50 A). Which rating must be selected per NEC requirements?