Objective. The learner installs an RPZ assembly on a training rig, correctly orients the relief valve port and discharge gap, and explains why the RPZ is required for high-hazard applications.
A reduced-pressure zone (RPZ) assembly — also called a reduced-pressure principle backflow preventer — is the highest-rated mechanical backflow preventer used in piped water systems. It is required wherever a cross-connection poses a high-hazard risk: that is, where backflow could introduce substances that are toxic, poisonous, or otherwise dangerous to health. Common high-hazard applications include irrigation systems using fertilizers or pesticides, fire-suppression systems with antifreeze or chemical additives, industrial process piping, medical equipment connections, and commercial boiler make-up water lines.
A double-check valve assembly (DCVA) is acceptable for low-hazard or non-health-threatening pollutant situations. When the hazard is health-threatening, codes require the RPZ. Understanding that distinction is central to both the ASSE Backflow credential and to keeping people safe.
The RPZ assembly contains three major internal components:
1. First check valve (upstream) — spring-loaded; opens only when supply pressure exceeds downstream pressure by a set differential.
2. Relief valve zone (middle chamber) — a pressure zone monitored by the differential-pressure relief valve. Under normal flow, pressure in this zone is lower than supply pressure but higher than the downstream side.
3. Second check valve (downstream) — spring-loaded; provides a second barrier against reverse flow.
The differential-pressure relief valve opens to atmosphere whenever the pressure in the middle zone drops to or below the supply pressure. This happens in two failure scenarios: if either check valve leaks, or if a backsiphonage or backpressure event occurs. When the relief valve opens, contaminated water is discharged to atmosphere rather than allowed to flow back into the potable supply. That is the safety action that makes the RPZ suitable for high-hazard connections — it physically vents the contamination path.
For the relief discharge to work, the relief port must face downward or toward a drain. Many manufacturers stamp an arrow or label the relief port side of the body. Always confirm orientation with the manufacturer's installation instructions and the applicable code (IPC or UPC). Mounting the relief port sideways or upward can flood the assembly housing and defeats the drainage function.
The discharge from the relief port must terminate with a code-required air gap above the flood-rim level of the receptor (floor drain or open funnel drain). An air gap is an unobstructed vertical distance between the relief valve outlet and the top of the drain receptor. Codes specify a minimum air gap — consult your applicable code book for the exact dimension required in your jurisdiction. The air gap ensures that if the drain backs up, wastewater cannot siphon back into the relief port.
An RPZ assembly must be installed level — side to side and end to end. An off-level assembly can cause the internal floats and springs to seat unevenly, causing nuisance relief valve weeping or check valve fouling. Use a spirit level on the body of the assembly after mounting.
Pipe supports must be placed on both the inlet and outlet piping so that the weight of the assembly is not carried by the joints alone. Copper, steel, or approved plastic support brackets, at code-required intervals, prevent joint stress and vibration fatigue. On a training rig, verify that the assembly does not rock or sag after you remove your hands.
After installation:
1. Close the downstream shut-off valve (isolating the assembly under test).
2. Slowly open the upstream shut-off valve to fill the assembly.
3. Watch the relief port — a correctly functioning assembly holds pressure without weeping from the relief port under static (no-flow) conditions.
4. Check all threaded joints for leaks using a dry cloth wipe.
5. Record your observations on the ASSE 5013 field test form (static observation section).
A weeping or dripping relief port during static no-flow conditions indicates a fouled or failed first check valve or an improperly seated relief valve — not acceptable; disassemble and inspect.
When reviewing case studies, apply this logic: Is the fluid on the downstream side a health hazard if it enters the potable supply? If yes, the RPZ is the required device. A DCVA provides two mechanical barriers but no relief-to-atmosphere path; it is not code-compliant on a high-hazard connection. Reviewing your IPC and UPC backflow sections will show you the hazard classification tables that distinguish high-hazard (RPZ required) from low-hazard (DCVA acceptable) connections.
Answer each question, then check it. Nothing is recorded; this is your own practice.