BLD-PLUM06-08 · Lesson 6 · 14 clock hours · lab

Double-Check Valve Assembly: Installation and Initial Inspection

Objective. The learner installs a double-check valve assembly on a training rig, aligns it to flow direction, sets test cocks to the closed position, and performs a visual initial inspection per ASSE field test procedure requirements.

Double-Check Valve Assembly: Installation and Initial Inspection

What Is a Double-Check Valve Assembly?

A double-check valve assembly (DCVA) is a backflow prevention device designed to protect potable water supplies from contamination under low-hazard, non-health-threatening conditions. Examples of low-hazard applications include lawn irrigation systems, commercial ice makers, and fire sprinkler systems supplied by a potable source where no toxic or chemical additives are present.

The DCVA contains two independently operating spring-loaded check valves arranged in series inside a single body. Each check valve opens when forward water pressure overcomes the spring, allowing water to flow in the intended direction. If downstream pressure rises above upstream pressure — a backpressure condition — or if upstream pressure drops below downstream pressure — a backsiphonage condition — both check valves seat tightly and block reverse flow. Requiring two check valves to fail simultaneously before contamination reaches the supply line is the key safety advantage of the DCVA over a simple single-check valve.

Component Overview

Understanding each part before installation prevents errors and speeds field troubleshooting:

Flow Direction and Orientation

Every DCVA body is marked with a flow-direction arrow cast or stamped into the body. Installing a DCVA backwards — against the arrow — means the check valves will be held open by forward flow rather than closing against it, rendering the device completely ineffective. Before threading a single union nut, confirm the arrow on the body points in the direction of intended water flow from supply to service.

DCVAs may be installed horizontally or vertically depending on the manufacturer's specifications and local code requirements. In horizontal installation, which is the most common, keep the test cocks positioned so a field tester can attach differential pressure gauge hoses without awkward angles. Consult the manufacturer's installation sheet and your Authority Having Jurisdiction (AHJ) for acceptable orientations.

Safety Before You Begin

Installation Procedure

1. Confirm flow direction on the rig piping by tracing the supply line. Mark an arrow on a piece of tape on the bench as a reference.

2. Position the DCVA body so its cast arrow aligns with the flow direction you identified.

3. Hand-thread both union joints — upstream first, then downstream — to confirm alignment before applying wrench force.

4. Torque unions evenly with a pipe wrench and backup wrench, following the torque value in the manufacturer's instructions or your instructor's direction for the training rig.

5. Confirm isolation valves on both sides are closed before slowly pressurizing for leak check.

6. Slowly open the upstream isolation valve a quarter-turn to introduce pressure gradually; listen and watch for leaks at unions.

7. Open the upstream isolation valve fully, then open the downstream isolation valve fully. The device is now in service.

8. Verify all test cocks are in the closed position (handle perpendicular to the body of the test cock).

Visual Initial Inspection

Before any differential pressure field test can be run, ASSE field test procedures require a visual initial inspection to confirm the device is properly installed and safe to test. On the ASSE form, you must document:

All fields must be complete before you proceed. An incomplete initial inspection form means the field test result is not valid for submittal to the AHJ. This is not a suggestion — it is an ASSE procedural requirement and a key competency for the ASSE Backflow certification exam.

Why This Matters for Your Career

Backflow incidents have caused documented illness outbreaks when unprotected cross-connections allowed fertilizers, industrial chemicals, or sewage to enter drinking water distribution. A correctly installed and inspected DCVA is the physical barrier that prevents this. As a licensed journeyman and ASSE-certified backflow tester, your signed field test report is a legal document. Getting installation and inspection right every time protects the public, protects your license, and is the foundation of ASSE Backflow certification.

Key terms10

Double-Check Valve Assembly (DCVA)A backflow prevention device containing two independently operating spring-loaded check valves in series, approved for low-hazard, non-health-threatening cross-connection conditions.
BackpressureA condition in which downstream pressure exceeds upstream supply pressure, potentially forcing water or contaminants backward into the potable supply.
BacksiphonageA condition in which a drop in upstream supply pressure creates a negative pressure (siphon effect) that draws downstream water or contaminants back into the supply line.
Test cockA small ball valve built into a backflow preventer body at designated test ports, used exclusively during field testing; kept closed at all other times.
Isolation valveA shutoff valve located immediately upstream and downstream of a backflow prevention assembly that allows the device to be isolated for testing or maintenance without disrupting the entire system.
Resilient discThe rubber or elastomeric seating element on a check valve that must contact its seat cleanly to form a watertight closure preventing reverse flow.
Visual initial inspectionThe documented pre-test examination of a backflow prevention assembly — checking orientation, components, and operability — required by ASSE field test procedures before any differential pressure test is performed.
Authority Having Jurisdiction (AHJ)The government body or official — typically a plumbing inspector or water purveyor — responsible for enforcing codes and approving the installation and testing of backflow prevention devices.
Union jointA three-part threaded pipe fitting that allows a section of pipe or device to be disconnected and reconnected without rotating the adjacent pipe, used on both ends of a DCVA for serviceability.
Low-hazard cross-connectionA point where the potable water supply connects to a non-potable system that poses no direct health risk (no toxic or biological contamination), for which a DCVA is an approved protective device.
In class: Instructor teardown demo: disassemble a DCVA to show both check valves, seats, and resilient discs; explain the role of each component in preventing back-flow under low-hazard conditions · Hands-on installation: learner installs a DCVA between two isolation valves on a training rig, aligns flow-direction arrow, torques unions, and positions test cocks correctly for future testing · Visual initial inspection: learner completes the ASSE initial inspection form, checking strainer, test cocks, isolation valves, and labeling before any test is run
Materials: DCVA assemblies (3/4-inch, 1-inch); training rig; pipe wrenches, adjustable wrench; union joints; ASSE field test procedure forms; ASSE 5013 (field test and maintenance manual for DCVAs); flow-direction reference cards
Check: Instructor visual inspection: flow direction correct, all test cocks operable, isolation valves functional, no leaks at unions; ASSE initial inspection form completed with no omissions (100% required for safety check)

Practice check8

Answer each question, then check it. Nothing is recorded; this is your own practice.

ASSE Backflow — Device selection and function
1. Which condition does a double-check valve assembly protect against by requiring two check valves to fail before contamination reaches the supply?
ASSE Backflow — Installation requirements
2. During installation of a DCVA on a training rig, a learner discovers the flow-direction arrow on the body points opposite to the direction of supply flow. What is the correct action?
ASSE Backflow — Device operation and maintenance
3. What is the correct position of test cocks on a DCVA that is in normal service and not being tested?
ASSE Backflow — Field test documentation
4. A learner completes the differential pressure field test but leaves the 'strainer present and accessible' field blank on the ASSE initial inspection form. What is the consequence?
ASSE Backflow — Device components and function
5. Which component of a DCVA is primarily responsible for preventing debris from holding a check valve disc off its seat?
ASSE Backflow — Installation safety and procedure
6. Before slowly opening the upstream isolation valve to pressurize a newly installed DCVA, what should the learner confirm?
ASSE Backflow — Device selection and cross-connection classification
7. A DCVA is an appropriate backflow prevention device for which of the following applications?
ASSE Backflow — Device inspection and maintenance
8. During the instructor teardown demonstration, the instructor shows that one resilient disc has a visible nick on its seating surface. What is the significance of this finding for backflow protection?