Focus Four: Electrocution Hazards

Objective. Learners will identify the electrocution hazards OSHA's Focus Four names (overhead power lines, missing ground-fault protection, a missing or broken path to ground, equipment used outside its listing, damaged or misused extension cords) and the 29 CFR 1926 Subpart K control for each.

⚠ Pending professional review

This lesson, its worked examples and its practice questions has not yet been verified by a licensed professional engineer or master tradesperson or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.

VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.

Focus Four: Electrocution Hazards

OSHA's Focus Four are the four hazard categories responsible for the majority of construction fatalities: falls, struck-by, caught-in/between, and electrocution. This lesson concentrates on electrocution. As an electrician, electrical hazards are your daily environment, which makes recognizing and controlling them a core professional duty, not an afterthought.

What 29 CFR 1926 Subpart K Covers

29 CFR 1926 Subpart K is the OSHA electrical standard for construction. It sets minimum requirements for electrical installations, equipment, and work practices on construction job sites. When you walk a site, Subpart K is the rulebook you apply.

Hazard 1: Overhead Power Lines

Uninsulated or energized overhead lines cause many electrocution deaths each year in construction. Workers make contact directly or through conductive equipment such as ladders, scaffold pipe, crane booms, or dump-truck beds.

Controls under Subpart K: Maintain at least a 10-foot clearance from lines rated 50 kV or below unless the utility has de-energized and visibly grounded the line, or insulating barriers acceptable to the utility are installed. For lines rated above 50 kV, clearance increases. Before any work begins near overhead lines, contact the utility, determine voltage, and establish a danger zone with warning flags or a spotter. Never assume a line is de-energized because it looks old or unused.

Hazard 2: Missing Ground-Fault Protection

A ground fault occurs when current finds an unintended path to ground — often through a worker's body. On construction sites, water, damaged insulation, and improvised wiring create ground-fault conditions constantly.

Controls under Subpart K: Subpart K requires ground-fault protection on all 120-volt, single-phase, 15- and 20-ampere receptacle outlets used by employees on construction sites. You meet this requirement one of two ways:

GFCI is simpler and preferred. The AEGCP is more paperwork-intensive and is used when GFCI is impractical for specific equipment.

How to test a GFCI: Plug a lamp or tester into the protected outlet. Press the TEST button — the outlet should go dead. Press RESET — power should return. If the outlet does not respond correctly, remove it from service immediately and tag it out.

Hazard 3: Missing or Broken Path to Ground (Equipment Grounding)

Metal housings of tools and equipment must be bonded to ground so that if a live conductor contacts the housing, fault current flows through the equipment grounding conductor — not through a worker — and trips the overcurrent device.

Controls under Subpart K: Inspect the grounding pin on every cord-and-plug connected tool before use. A missing or bent grounding pin, a cut grounding wire inside the cord, or a broken cord cap removes that protection. Apply lockout/tagout (LOTO), remove the tool from service, and tag it clearly. Never remove the grounding pin to fit a two-prong outlet. Use only equipment that is properly listed and labeled by a nationally recognized testing laboratory (NRTL) such as UL or CSA.

Hazard 4: Equipment Used Outside Its Listing

Equipment is listed and labeled for specific conditions of use — voltage, amperage, indoor/outdoor, wet/dry locations. Using equipment outside those conditions voids its listing and creates an uncontrolled hazard.

Controls under Subpart K: Read the label. A cord or tool marked for indoor use only must not be used in rain or standing water. Extension cords must be rated for the load and environment. Three-wire cords are required for tools with a grounding path. Check ampacity ratings — an undersized cord overheats, damages insulation, and can ignite materials nearby.

Hazard 5: Damaged or Misused Extension Cords

Extension cords on construction sites are abused: driven over, pinched in doors, repaired with tape, overloaded, and daisy-chained. Each abuse is a potential electrocution or fire.

Controls under Subpart K: Inspect every cord before each use. Remove from service any cord with: cracked or cut insulation, exposed conductors, a damaged or missing grounding pin, a repaired jacket that is not factory quality, or burn marks. Use the cord for its rated ampacity only. Do not use household extension cords (typically 16 AWG) to power high-draw tools. Route cords safely — overhead where possible, not under mats where wear is hidden.

Lockout/Tagout and PPE

Before working on or near any electrical equipment, follow your site's LOTO procedure: de-energize, isolate, lock, tag, test for absence of voltage with a properly rated voltage tester. Wear voltage-rated PPE appropriate to the task: safety glasses, insulated gloves rated for the voltage, and arc-flash protective clothing where arc-flash hazard exists. Never rely on one layer of protection alone.

Photo Walk Summary

When walking a job-site photo for hazards, look systematically: trace every cord from tool to outlet, check clearances from overhead lines, look for missing covers and open junction boxes, verify GFCI devices are present and functional, and check that all tools carry NRTL labels. Document what you find and report it to your supervisor before work resumes.

Key terms8

Focus FourOSHA's four hazard categories — falls, struck-by, caught-in/between, and electrocution — that account for the majority of construction fatalities.
29 CFR 1926 Subpart KThe OSHA electrical standard for construction sites, covering installation requirements, equipment, and safe work practices.
Ground-Fault Circuit Interrupter (GFCI)A protective device that continuously monitors the current balance between hot and neutral conductors and opens the circuit within milliseconds when it detects a ground-fault current, protecting workers from electrocution.
Assured Equipment Grounding Conductor Program (AEGCP)A written, employer-managed alternative to GFCI protection that requires a competent person, documented visual inspections, and regular electrical testing of all cord-and-plug connected equipment.
Equipment Grounding ConductorThe conductor — typically the green wire or bare copper — that bonds the metal housing of tools and equipment to ground, providing a low-impedance path for fault current and causing the overcurrent device to trip.
NRTL (Nationally Recognized Testing Laboratory)A laboratory accredited by OSHA to test and certify electrical equipment to applicable safety standards; examples include UL and CSA. Equipment must carry an NRTL listing mark to be used legally on construction sites.
Lockout/Tagout (LOTO)A set of procedures that de-energizes equipment and prevents re-energization during servicing or maintenance by using physical locks and warning tags on energy-isolation points.
Minimum Approach DistanceThe closest a worker or conductive object may come to an energized overhead power line without additional protective measures; at least 10 feet for lines rated 50 kV or below under OSHA construction rules.
In class: Walk a photo job site and mark every electrical hazard. · Inspect damaged extension cords and decide which come out of service. · Test a GFCI and compare GFCI protection with an assured equipment grounding conductor program.
Materials: 29 CFR 1926 Subpart K; GFCI tester; sample cords; OSHA Focus Four electrocution handout
Check: Names each hazard with a correct control, tests a GFCI correctly, and scores 80% on the lesson quiz.

Practice check8

Answer each question, then check it. Nothing is recorded; this is your own practice.

OSHA 30 Construction — Focus Four: Electrocution
1. Under 29 CFR 1926 Subpart K, what is the minimum clearance a worker must maintain from an energized overhead power line rated at 50 kV or below?
OSHA 30 Construction — Focus Four: Electrocution
2. A worker presses the TEST button on a GFCI outlet and the connected lamp stays lit. What is the correct action?
OSHA 30 Construction — Focus Four: Electrocution
3. Which of the following is an acceptable alternative to GFCI protection for 120-volt, 15-ampere receptacles on a construction site under Subpart K?
OSHA 30 Construction — Focus Four: Electrocution
4. A cord-and-plug connected drill has its grounding pin broken off. What is the hazard and the correct response?
OSHA 30 Construction — Focus Four: Electrocution
5. Which of the following extension cord conditions requires the cord to be immediately removed from service?
OSHA 30 Construction — Focus Four: Electrocution
6. A crew is setting up for concrete work. The utility has not been contacted and overhead lines run directly above the work area. What Focus Four electrocution hazard does this represent and what is the first control step?
OSHA 30 Construction — Focus Four: Electrocution
7. An electrician finds a power tool on site that has no listing mark from any nationally recognized testing laboratory. Under Subpart K, this tool falls under which Focus Four electrocution hazard category?
OSHA 30 Construction — Focus Four: Electrocution
8. Before testing a circuit for absence of voltage as part of a lockout/tagout procedure, what must the electrician verify about the voltage tester being used?