Objective. Learners will identify the electrocution hazards OSHA's Focus Four names (overhead power lines, missing ground-fault protection, a missing or broken path to ground, equipment used outside its listing, damaged or misused extension cords) and the 29 CFR 1926 Subpart K control for each.
This lesson, its worked examples and its practice questions has not yet been verified by a licensed professional engineer or master tradesperson or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.
VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.
OSHA's Focus Four are the four hazard categories responsible for the majority of construction fatalities: falls, struck-by, caught-in/between, and electrocution. This lesson concentrates on electrocution. As an electrician, electrical hazards are your daily environment, which makes recognizing and controlling them a core professional duty, not an afterthought.
29 CFR 1926 Subpart K is the OSHA electrical standard for construction. It sets minimum requirements for electrical installations, equipment, and work practices on construction job sites. When you walk a site, Subpart K is the rulebook you apply.
Uninsulated or energized overhead lines cause many electrocution deaths each year in construction. Workers make contact directly or through conductive equipment such as ladders, scaffold pipe, crane booms, or dump-truck beds.
Controls under Subpart K: Maintain at least a 10-foot clearance from lines rated 50 kV or below unless the utility has de-energized and visibly grounded the line, or insulating barriers acceptable to the utility are installed. For lines rated above 50 kV, clearance increases. Before any work begins near overhead lines, contact the utility, determine voltage, and establish a danger zone with warning flags or a spotter. Never assume a line is de-energized because it looks old or unused.
A ground fault occurs when current finds an unintended path to ground — often through a worker's body. On construction sites, water, damaged insulation, and improvised wiring create ground-fault conditions constantly.
Controls under Subpart K: Subpart K requires ground-fault protection on all 120-volt, single-phase, 15- and 20-ampere receptacle outlets used by employees on construction sites. You meet this requirement one of two ways:
GFCI is simpler and preferred. The AEGCP is more paperwork-intensive and is used when GFCI is impractical for specific equipment.
How to test a GFCI: Plug a lamp or tester into the protected outlet. Press the TEST button — the outlet should go dead. Press RESET — power should return. If the outlet does not respond correctly, remove it from service immediately and tag it out.
Metal housings of tools and equipment must be bonded to ground so that if a live conductor contacts the housing, fault current flows through the equipment grounding conductor — not through a worker — and trips the overcurrent device.
Controls under Subpart K: Inspect the grounding pin on every cord-and-plug connected tool before use. A missing or bent grounding pin, a cut grounding wire inside the cord, or a broken cord cap removes that protection. Apply lockout/tagout (LOTO), remove the tool from service, and tag it clearly. Never remove the grounding pin to fit a two-prong outlet. Use only equipment that is properly listed and labeled by a nationally recognized testing laboratory (NRTL) such as UL or CSA.
Equipment is listed and labeled for specific conditions of use — voltage, amperage, indoor/outdoor, wet/dry locations. Using equipment outside those conditions voids its listing and creates an uncontrolled hazard.
Controls under Subpart K: Read the label. A cord or tool marked for indoor use only must not be used in rain or standing water. Extension cords must be rated for the load and environment. Three-wire cords are required for tools with a grounding path. Check ampacity ratings — an undersized cord overheats, damages insulation, and can ignite materials nearby.
Extension cords on construction sites are abused: driven over, pinched in doors, repaired with tape, overloaded, and daisy-chained. Each abuse is a potential electrocution or fire.
Controls under Subpart K: Inspect every cord before each use. Remove from service any cord with: cracked or cut insulation, exposed conductors, a damaged or missing grounding pin, a repaired jacket that is not factory quality, or burn marks. Use the cord for its rated ampacity only. Do not use household extension cords (typically 16 AWG) to power high-draw tools. Route cords safely — overhead where possible, not under mats where wear is hidden.
Before working on or near any electrical equipment, follow your site's LOTO procedure: de-energize, isolate, lock, tag, test for absence of voltage with a properly rated voltage tester. Wear voltage-rated PPE appropriate to the task: safety glasses, insulated gloves rated for the voltage, and arc-flash protective clothing where arc-flash hazard exists. Never rely on one layer of protection alone.
When walking a job-site photo for hazards, look systematically: trace every cord from tool to outlet, check clearances from overhead lines, look for missing covers and open junction boxes, verify GFCI devices are present and functional, and check that all tools carry NRTL labels. Document what you find and report it to your supervisor before work resumes.
Answer each question, then check it. Nothing is recorded; this is your own practice.
A free tech program — complimentary, as our commitment to get America working. Help us build VoTechWorks. Tell us what works, what doesn’t, and what you want to learn.
Does the school offer financial aid?
No. We don’t offer financial aid because we’re free. No, really: completely free.
Do you offer industry certification?
No. We are not certified yet, so we can’t offer that to students. What we do offer is knowledge and understanding of a trade.
Enroll first in the trade you’re interested in. You get your key, your program opens, and you begin studying.
Enroll free →