Objective. Learners will solve a set of twenty-five multi-step calculation problems representative of those appearing on state journeyman licensing exams — including service load calculations, branch-circuit sizing, voltage-drop calculations, motor branch-circuit and overload protection sizing, and conduit fill — achieving a minimum accuracy of 75 percent under timed exam conditions.
State journeyman licensing exams are heavily calculation-based. Examiners test whether you can open the NEC, locate the correct table or section, apply the right multiplier, and arrive at a code-compliant answer — all under a fixed time limit. A score below the passing threshold means you leave without a license, regardless of your field experience. This lab replicates those exact conditions so that exam day feels familiar, not foreign.
Every calculation type covered here appears in the NEC and in standard journeyman exam question banks: service load calculations, branch-circuit sizing, voltage-drop, motor branch-circuit protection, and conduit fill. Learn the workflow for each type, not just the answer.
Service load calculations determine the minimum ampacity a service must supply for a dwelling or commercial occupancy. For dwelling units, Article 220 of the NEC provides the method. The general lighting load is calculated from the floor area multiplied by a unit load (volt-amperes per square foot) found in NEC Table 220.12. Demand factors from Table 220.42 are then applied to the general lighting load — the first portion of the load is taken at 100 percent, the remainder at a reduced percentage. Add fixed appliance loads, the larger of the heating or air-conditioning load, and the nameplate load of large appliances. Divide the total volt-amperes by the system voltage to find the minimum service amperes, then select the next standard ampere rating from NEC 240.6(A).
Key habit: never skip the demand factor step. Applying 100 percent to the entire lighting load overstates the service size and wastes the client's money; worse, omitting demand factors entirely can lead to an undersized service.
Branch-circuit conductors must have an ampacity not less than the maximum load to be served (NEC 210.19). Conductor ampacity is read from NEC Table 310.12 for dwelling units or Table 310.16 for most other applications. Always identify the correct temperature column (60 °C, 75 °C, or 90 °C) based on the equipment terminal rating — most residential devices are rated 60 °C; most commercial devices are rated 75 °C. Misreading the column is one of the most common exam errors.
After finding ampacity, check whether a conductor ampacity adjustment is required for more than three current-carrying conductors in a raceway (NEC 310.15(C)(1)). Multiply the table ampacity by the correction factor before comparing to the load.
Voltage drop is not strictly mandated by the NEC for branch circuits, but NEC 210.19(A) Informational Note recommends keeping it to 3 percent for branch circuits and 5 percent total for feeders and branch circuits combined. Exam problems use the standard formula:
VD = (K × I × L) / CM
Where K = 12.9 for copper (or 21.2 for aluminum), I = current in amperes, L = one-way length in feet, and CM = circular-mil area of the conductor. Rearrange to solve for CM when the problem asks for the minimum conductor size, then look up the next larger standard conductor in Table 9 (Chapter 9) or Table 310.16.
Motor circuits follow Article 430, which has its own sizing rules separate from Article 210. The design sequence is:
1. Find the motor full-load amperes (FLA) from NEC Tables 430.247–430.250 — do not use the nameplate running current for sizing purposes unless the problem states otherwise.
2. Size the branch-circuit short-circuit and ground-fault protection device at the percentage of FLA listed in Table 430.52 (e.g., inverse-time breaker: 250 percent of FLA for a standard motor). If that value does not match a standard breaker size, round up to the next standard size, but not above the next higher percentage limit in 430.52.
3. Size the overload protection device at no more than 115 or 125 percent of the nameplate full-load current, depending on the service factor or temperature rise, per NEC 430.32(A)(1).
4. Size the branch-circuit conductors at no less than 125 percent of the motor FLA per NEC 430.22.
Do not confuse the overload device with the branch-circuit overcurrent device — they protect different things.
NEC Chapter 9, Table 1 sets maximum fill percentages: 53 percent for one conductor, 31 percent for two conductors, and 40 percent for three or more conductors. Look up each conductor's cross-sectional area in Chapter 9, Annex C tables. Sum the areas, divide by the maximum permitted fill percentage, and select the smallest conduit whose interior area is equal to or greater than the result. Annex C provides pre-calculated tables that speed this up on the exam.
This is a paper-and-calculator lab, but the NEC values you are practicing protect people's lives in the field. An undersized conductor overheats and starts fires. An oversized overcurrent device fails to clear a fault. A forgotten voltage-drop correction leaves motors running hot and failing early. Treat every arithmetic error as a potential field hazard, not just a missed point.
When you later apply these calculations in the field, always follow lockout/tagout (LOTO) procedures before touching any conductor or panel, and wear appropriate PPE — at minimum, safety glasses and arc-flash-rated PPE selected based on the incident energy level of the equipment. Your calculation skills and your safety habits must both be exam-ready.
State journeyman exams allocate a fixed total time across all questions. Divide your time evenly per question and move on if you are stuck — return to hard problems last. Keep your NEC tabbed for the sections most tested: Articles 210, 220, 240, 310, 430, and Chapter 9. Practice finding each table in under thirty seconds.
Answer each question, then check it. Nothing is recorded; this is your own practice.
A free tech program — complimentary, as our commitment to get America working. Help us build VoTechWorks. Tell us what works, what doesn’t, and what you want to learn.
Does the school offer financial aid?
No. We don’t offer financial aid because we’re free. No, really: completely free.
Do you offer industry certification?
No. We are not certified yet, so we can’t offer that to students. What we do offer is knowledge and understanding of a trade.
Enroll first in the trade you’re interested in. You get your key, your program opens, and you begin studying.
Enroll free →