Objective. Learners will accurately convert between imperial and metric units, perform percentage calculations, and apply Ohm's Law and the power formula to solve wire-sizing and load problems typical of distribution line work.
This lesson, its worked examples and its practice questions has not yet been verified by a licensed professional engineer or master tradesperson or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.
VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.
Electrical lineworkers make decisions that affect public safety every shift. An error in a load calculation can overload a transformer. A wrong unit conversion can produce a wire that overheats under load. Accurate arithmetic is as important as correct PPE — both protect lives. This lesson builds the calculation skills you will use daily on distribution systems and that appear on the NCCER Power Line Worker assessments.
The electrical trade uses both systems. Wire sizes are expressed in American Wire Gauge (AWG) or in circular mils. Distances are often in feet and miles for line work but in meters and millimeters in equipment specifications. You must move between systems without error.
Key conversion facts:
To convert, multiply or divide by the conversion factor. Write units in every step so they cancel correctly. If you see the same unit in the numerator and denominator, it cancels — what remains is your answer's unit. This technique is called dimensional analysis and it catches most unit errors before they cost you.
Percentage problems appear in load calculations and in voltage-drop checks. The basic relationship is:
Part = Percent × Whole (where percent is expressed as a decimal)
To find what percentage one value is of another: divide the part by the whole, then multiply by 100.
Example use: a transformer is rated for 167 kVA. The connected load is 134 kVA. Load percentage = (134 ÷ 167) × 100 = 80.2%. Keeping load below 100% of nameplate rating prevents overheating.
Ohm's Law states the relationship among voltage (V), current (I), and resistance (R) in a DC circuit or in a single-phase AC circuit treated as resistive:
V = I × R
Rearranged:
A useful memory aid is the Ohm's Law triangle: write V on top, I and R on the bottom. Cover the unknown to see the formula for it.
Units: voltage in volts (V), current in amperes (A), resistance in ohms (Ω).
Safety note: Even low voltages can drive lethal current through the body if resistance is low. At 120 V, wet skin resistance can fall low enough to allow current well above the fibrillation threshold. Always treat every conductor as energized until lockout/tagout (LOTO) is confirmed and absence of voltage is verified with a tested meter.
Electrical power in watts relates to voltage and current:
P = V × I
Rearranged:
For three-phase systems (common in distribution work), the formula becomes:
P = √3 × V_line × I_line × power factor
For single-phase problems in this course, use P = V × I unless a power factor is specified.
Kilovolt-amperes (kVA) is used for transformer ratings because it does not assume a power factor. 1 kVA = 1,000 VA. For purely resistive loads, kW and kVA are numerically equal.
As current flows through a conductor, resistance in the wire causes a voltage drop. The basic formula for a single-phase, two-wire circuit is:
V_drop = 2 × I × R_wire
The factor of 2 accounts for both the outgoing and return conductors. R_wire depends on conductor material, cross-sectional area, and length — values found in conductor tables in your reference text. Excessive voltage drop causes motors to overheat and lights to dim. Distribution standards typically limit voltage drop to a small percentage of system voltage; always check the applicable utility specification.
Wire must carry the load current without overheating. A larger AWG number means a smaller wire (AWG 2 is larger than AWG 6). For distribution conductors, ampacity tables in your reference give the maximum continuous current for each conductor size and insulation type. Always confirm the correct table for overhead vs. underground and for the ambient temperature of the installation.
Every formula result should pass a reasonableness check: if your calculated current for a residential service is 10,000 A, you made an error — stop and find it. On the job, an unchecked error can mean selecting undersized wire that overloads and fails, or setting a fuse rating too high to protect the circuit. Math errors in line work have caused fires and fatalities. Build the habit of checking units, checking magnitude, and having a qualified person verify critical calculations.
Answer each question, then check it. Nothing is recorded; this is your own practice.
A free tech program — complimentary, as our commitment to get America working. Help us build VoTechWorks. Tell us what works, what doesn’t, and what you want to learn.
Does the school offer financial aid?
No. We don’t offer financial aid because we’re free. No, really: completely free.
Do you offer industry certification?
No. We are not certified yet, so we can’t offer that to students. What we do offer is knowledge and understanding of a trade.
Enroll first in the trade you’re interested in. You get your key, your program opens, and you begin studying.
Enroll free →