Objective. Students will explain the purpose and wiring function of time-delay-on-break, time-delay-on-make, defrost time-clock, and heat-sequencer controls in HVAC/R applications and correctly wire a time-delay relay into a training circuit.
Every refrigeration compressor, electric heating system, and commercial refrigeration case depends on carefully timed switching events. If a compressor restarts too soon after shutdown, high discharge pressure and low suction pressure can combine to overload the motor — a condition called short cycling. If a heat pump's electric strips energize all at once, the inrush current can trip a breaker. Timing controls solve these problems by intentionally delaying or sequencing switching events. This lesson covers four of the most important: the time-delay-on-make (TDOM), time-delay-on-break (TDOB), the defrost time-clock control, and the heat sequencer.
A time-delay relay (TDR) is an electromechanical or solid-state device that introduces a controlled pause between a coil energizing (or de-energizing) and the movement of its contacts. Two types appear repeatedly in HVAC/R ladder diagrams.
Time-Delay-On-Make (TDOM) — also called Delay-On-Energize (TDOE) in some manufacturer literature. When coil voltage is applied, the contacts wait for the set delay period before switching. Only after that delay does the load circuit close. Application example: holding the condenser fan off for a short period at startup to allow refrigerant pressures to equalize, or preventing a compressor from energizing for a set period after a thermostat call. In ladder diagrams, a TDOM contact is drawn with a small timing arrow pointing toward the contact.
Time-Delay-On-Break (TDOB) — also called Delay-On-De-Energize (TDOD). The contacts switch immediately when the coil is energized, but when coil voltage is removed the contacts hold their position for the set delay period before returning to normal. Application example: anti-short-cycle protection. When the thermostat is satisfied and drops the compressor contactor out, a TDOD relay keeps a lockout contact open (or closed, depending on wiring) long enough to prevent the compressor from restarting until pressures have had time to equalize — typically three to five minutes, though the exact period is set by the technician.
In a typical split-system ladder diagram, the thermostat Y terminal feeds both the compressor contactor coil and the coil of a TDOD relay wired in parallel. The normally-open (NO) timed contact of the TDOD relay is placed in series with the compressor contactor coil. Here is the sequence:
1. Thermostat calls for cooling → Y energizes → TDOD relay coil energizes → its NO timed contact closes immediately (TDOD contacts move immediately on energize) → compressor contactor pulls in.
2. Thermostat is satisfied → Y de-energizes → TDOD coil loses power → timed contact stays closed for the set delay → compressor contactor stays out because the thermostat has already dropped.
3. After the delay period, the TDOD contact opens, resetting for the next cycle.
If the thermostat calls again before the delay expires, the compressor cannot start until the timer resets — that is the protection.
Commercial refrigeration cases accumulate frost on evaporator coils. Periodic defrost cycles melt that frost so airflow and efficiency are maintained. The defrost time-clock is a 24-hour (or programmable) motor-driven clock that initiates defrost at preset times — commonly two to four times daily for medium-temperature cases.
The typical defrost sequence in a reach-in cooler proceeds through five events:
1. Initiation — The time-clock contacts close, removing power from the compressor/evaporator fan circuit and energizing the defrost heaters.
2. Heater operation — Electric heaters melt frost off the coil.
3. Termination by temperature — A defrost termination thermostat (also called a high-limit thermostat) senses coil temperature; when it reaches its set point (often around 55 °F, though the exact value is set by the equipment manufacturer), it opens and ends the defrost heater cycle.
4. Drip-down period — The evaporator fan is held off for a short time (controlled by a fan-delay thermostat or timer) while meltwater drains, preventing wet air from entering the case.
5. Return to refrigeration — The time-clock or termination thermostat restores normal refrigeration operation; fans restart after the coil cools.
If frost load is heavy and termination temperature is never reached, a safety time-out built into the time-clock terminates defrost anyway, preventing case temperature from rising too high.
Electric furnaces and air handlers use multiple heating elements — sometimes three or more. Energizing all elements simultaneously creates a large inrush current that can trip breakers or cause voltage sag. A heat sequencer is a bimetal-strip device heated by a small resistance heater. As the bimetal warms, it closes successive contacts at timed intervals — typically a few seconds to several tens of seconds apart — staging the heating elements on one at a time. Multiple sequencers can be chained: the last contact of the first sequencer energizes the coil of the next, creating a cascade. On shutdown, the bimetal cools and opens contacts in reverse order, also sequentially.
Answer each question, then check it. Nothing is recorded; this is your own practice.
A free tech program — complimentary, as our commitment to get America working. Help us build VoTechWorks. Tell us what works, what doesn’t, and what you want to learn.
Does the school offer financial aid?
No. We don’t offer financial aid because we’re free. No, really: completely free.
Do you offer industry certification?
No. We are not certified yet, so we can’t offer that to students. What we do offer is knowledge and understanding of a trade.
Enroll first in the trade you’re interested in. You get your key, your program opens, and you begin studying.
Enroll free →