BLD-HVAC07-07 · Lesson 6 · 18 clock hours · lab
Evaporators, Defrost Systems, and Display Case Service
Objective. Students will service a commercial display-case evaporator coil by inspecting fin condition, testing defrost heaters with a multimeter, verifying defrost termination and fan delay operation, and documenting results on a service form.
Evaporators, Defrost Systems, and Display Case Service
The Role of the Evaporator in a Commercial Display Case
The evaporator coil is the heart of any refrigerated display case. Refrigerant enters the coil as a low-pressure liquid-vapor mixture, absorbs heat from the cabinet air, and leaves as a low-pressure vapor. Fans pull air across the finned coil, maintaining the cabinet temperature the product requires. When the evaporator cannot transfer heat efficiently — because fins are blocked with ice or frost, fan blades are damaged, or airflow is restricted — cabinet temperature rises and product is at risk.
Commercial reach-in cases operate in humid store environments. Every time a door opens, warm moist air enters and moisture condenses or freezes on the cold coil. Without a properly functioning defrost system, ice accumulates until airflow is nearly zero.
Defrost System Fundamentals
Electric defrost is the most common method in reach-in cases. During a defrost cycle the compressor and evaporator fans shut off, and electric resistance heaters — embedded in or clipped to the coil — energize and melt accumulated frost. Meltwater drains through a drain pan, which also contains a drain-pan heater to keep the drain line clear.
Two controls manage the cycle:
- Defrost initiation: A mechanical (clock-type) timer or electronic control board starts defrost at scheduled intervals, typically two to six times per day depending on the application and door traffic.
- Defrost termination: A termination thermostat (sometimes called a high-limit thermostat) senses coil temperature. When the coil reaches the setpoint — indicating ice is cleared — it opens the heater circuit and ends the cycle early, preventing overheating. A backup time cutout also terminates defrost if the thermostat fails to open.
After defrost, a fan delay thermostat (or fan delay built into the control board) holds the evaporator fans off until the coil temperature drops back to a safe operating range. This prevents blowing warm air into the cabinet.
Evaporator Fan Assembly Inspection and Motor Testing
Before touching any electrical component, follow lockout/tagout (LOTO) procedures: de-energize the case, apply an approved lockout device to the disconnect, and verify zero energy with a meter. Wear safety glasses throughout.
To inspect the fan assembly:
1. Remove the evaporator cover panel to expose the fan deck.
2. Inspect fan blades for cracks, ice erosion, or debris. A bent blade causes vibration that accelerates bearing wear.
3. Spin the motor shaft by hand — it should turn freely with no roughness or catching, which would indicate failing bearings.
4. With LOTO applied and the circuit isolated, set your digital multimeter (DMM) to the ohms (Ω) function. Measure resistance across the motor winding terminals. Compare the reading to the motor nameplate or manufacturer specification. An open winding reads OL (overload/infinite resistance); a shorted winding reads near zero. Either condition means the motor must be replaced.
5. Check resistance from each winding terminal to the motor frame (ground). Any measurable low resistance to ground indicates insulation breakdown — replace the motor.
Testing Electric Defrost Heaters
With LOTO applied and heater leads disconnected from the circuit:
1. Set your DMM to ohms. Measure resistance across each heater element. A typical commercial defrost heater reads a low but measurable resistance (the actual value depends on heater wattage and design — record the reading and compare to the nameplate or manufacturer data).
2. Test continuity. An OL reading means the heater element is open and must be replaced.
3. Test each heater from terminal to case ground. Any low resistance to ground indicates a failed heater with compromised insulation — replace it.
4. After reassembly and restoration of power, use a clamp ammeter around one heater lead during an initiated defrost cycle to confirm the heater is drawing current. Compare the measured amperage to the expected value calculated from nameplate wattage and supply voltage.
Testing the Defrost Termination Thermostat
The termination thermostat is a normally closed switch that opens on temperature rise. At room temperature the thermostat should show continuity (closed). If the coil is warm enough to be above its setpoint, the thermostat will read open — this is normal. To confirm function: with LOTO applied and the thermostat disconnected, check continuity at room temperature (expect closed/continuity). Warm the sensing bulb gently with your hand or a warm cloth and recheck — it should open at or near its rated setpoint. A thermostat that never opens allows defrost to run too long; one that is stuck open prevents defrost from starting through the heater circuit.
Diagnosing Ice Build-Up
Excessive ice on the evaporator coil is always a symptom, not a root cause. Common causes include:
- Door gasket failure: Worn or torn gaskets allow warm humid air to enter continuously, overloading the defrost system.
- Defrost timer or control malfunction: Defrost may not be initiating or may be terminating too early.
- Drain line blockage: Meltwater backs up and refreezes on the coil.
- Defrost heater failure: Insufficient heat to clear the coil.
- Fan delay thermostat failure: Fans restart before the coil is cold, circulating warm air and adding moisture load.
Diagnosis follows a logical sequence: interview the operator about symptoms and history, inspect gaskets, verify defrost timer operation and cycle count, check drain pan and drain line, then test electrical components.
Documentation
Every service call requires a complete service form. Record all measured resistance and amperage values, the defrost cycle start and termination temperatures and times, your root-cause determination, and corrective actions taken or recommended. Accurate documentation protects the technician, supports warranty claims, and gives the next technician a clear history.
Key terms8
Defrost termination thermostatA temperature-actuated switch that opens the defrost heater circuit when the evaporator coil reaches a set temperature, ending the defrost cycle and preventing overheating.
Fan delay thermostatA control that holds evaporator fans off after defrost ends until the coil cools to a safe temperature, preventing warm air from being circulated into the cabinet.
Electric defrost heaterA resistance heating element installed in or near the evaporator coil that energizes during defrost to melt accumulated frost and ice.
Lockout/tagout (LOTO)An OSHA-required safety procedure that de-energizes equipment and prevents re-energization while technicians are working on electrical or mechanical components.
Winding resistanceThe measured ohmic resistance of a motor's coil windings; used to identify open windings, shorted windings, or ground faults in an electric motor.
Clamp ammeterA meter that measures alternating current by clamping around a single conductor without breaking the circuit, used here to verify heater current draw during defrost.
Defrost timerA mechanical or electronic device that initiates defrost at preset intervals and provides a backup time cutout if the termination thermostat fails to open the circuit.
Drain-pan heaterA low-wattage resistance heater located in the evaporator drain pan that keeps the pan and drain line warm to prevent meltwater from refreezing.
Worked examples4
1. A defrost heater is rated 500 W at 240 V. What resistance should you expect to measure across its terminals when it is at room temperature and disconnected from the circuit?
- Use the power formula rearranged for resistance: R = V² ÷ P
- Substitute the known values: R = 240² ÷ 500
- Calculate the numerator: 240 × 240 = 57,600
- Divide: 57,600 ÷ 500 = 115.2 Ω
Answer: You should expect to measure approximately 115 Ω across the heater terminals. A reading significantly higher indicates a partially failed element; OL (infinite) means the element is open and must be replaced.
2. During a defrost cycle you clamp your ammeter around one lead of the same 500 W, 240 V heater. What current draw should you expect if the heater is functioning correctly?
- Use the formula: I = P ÷ V
- Substitute: I = 500 ÷ 240
- Calculate: I = 2.08 A
Answer: A properly functioning heater should draw approximately 2.1 A. A reading of 0 A with voltage present means the heater circuit is open (failed heater, open termination thermostat, or wiring fault).
3. A reach-in case has two defrost heaters in parallel: Heater A is 400 W and Heater B is 600 W, both rated at 240 V. What is the combined current draw you would expect to measure at the main defrost circuit supply lead?
- Calculate total wattage: 400 + 600 = 1,000 W
- Use I = P ÷ V: I = 1,000 ÷ 240
- Calculate: I = 4.17 A
Answer: The combined current draw should be approximately 4.2 A. If your clamp ammeter reads significantly less, one heater element is likely open; if it reads zero, the entire defrost circuit has failed to energize.
4. An evaporator fan motor nameplate lists winding resistance as 18 Ω. Your DMM reads 54 Ω across the winding terminals. What does this indicate?
- Compare the measured value (54 Ω) to the nameplate specification (18 Ω).
- The measured resistance is three times the expected value — it is not an open circuit (OL) and not a short (near 0 Ω).
- A resistance significantly higher than specification, but not infinite, typically indicates corroded or high-resistance connections in the winding circuit, partial winding damage, or a bad connection at the terminals.
- Inspect terminal connections for corrosion first; if connections are clean, the motor winding is suspect and the motor should be replaced.
Answer: The motor winding resistance is abnormally high compared to nameplate data. After ruling out corroded terminals, the motor should be replaced. Do not return a motor to service with out-of-specification winding resistance.
The math in this lesson1
Learners use R = V²/P and I = P/V to predict defrost heater resistance and amp draw.
A-CED.4
In class: Students remove an evaporator fan assembly from a training reach-in case, inspect blades and motor bearings, measure motor winding resistance, reassemble, and record findings on a service form. · Defrost system testing: using a multimeter, students test continuity and resistance of electric defrost heaters, check the defrost termination thermostat, and verify the defrost timer or electronic control initiates and terminates a defrost cycle correctly. · Ice-blockage scenario: instructor introduces simulated ice build-up (foam prop) on an evaporator coil; students photograph, diagnose root cause from a symptom list (door gasket failure, defrost timer malfunction, drain line blockage), and write a corrective action summary.
Materials: Reach-in training cases with electric defrost, digital multimeters, manifold gauge sets, clamp ammeter, defrost timer (mechanical and electronic), thermocouples, service forms, screwdrivers, nut drivers, NCCER HVAC Trainee Guide Level 3
Check: Instructor evaluates service form: all measured values recorded, defrost cycle verification documented, and root-cause diagnosis correct. Pass requires accurate data and a defensible written corrective action.
Practice check8
Answer each question, then check it. Nothing is recorded; this is your own practice.