Objective. Students use room-by-room load calculation results to determine required CFM for each room and identify trunk and branch duct sizes from Manual D friction rate charts, producing a duct sizing summary sheet for the residential case study.
A duct system is not sized by guesswork or rule of thumb. It is sized to deliver exactly the right amount of conditioned air to each room so the equipment can maintain design indoor conditions. That connection — from Manual J load to Manual D duct size — is the foundation of this lesson.
ACCA Manual J gives you the sensible and latent heat load for every room. Once you have selected equipment (Manual S), you know the total system airflow in cubic feet per minute (CFM). Manual D then tells you how to distribute that airflow through a duct network so each room receives its proportional share.
The fraction of total system airflow each room needs equals the fraction of total sensible load that room represents. The formula is:
Room CFM = (Room Sensible BTU/h ÷ System Sensible BTU/h) × Total System CFM
For example, if the whole house has a design sensible cooling load of 24,000 BTU/h and the selected equipment delivers 1,000 CFM, a bedroom with a sensible load of 3,600 BTU/h needs:
(3,600 ÷ 24,000) × 1,000 = 150 CFM
Repeat this calculation for every room and record the results on your CFM summary sheet. The sum of all room CFMs must equal total system CFM. If it does not, recheck your arithmetic before proceeding.
Once you know how much air each room needs, you size the ducts to deliver it. Manual D uses the friction rate method, which works in two parts.
Available Static Pressure (ASP): Every air-handling unit has a rated external static pressure — the pressure it can overcome while moving air. From that rated value you subtract the pressure drops caused by coils, filters, grilles, registers, and any factory accessories. What remains is the pressure budget available to push air through the duct system itself.
Total Effective Length (TEL): The longest supply or return duct path from the air handler to the farthest terminal is measured. Fittings (elbows, tees, transitions) are converted to equivalent straight lengths using tables in Manual D and added to the actual straight length. This gives the TEL for the critical path.
Design Friction Rate (FR): Dividing the available static pressure by the TEL gives the friction rate in inches of water column per 100 feet of duct (in. w.c./100 ft). This single number is your sizing target for every duct in the system.
FR = Available Static Pressure (in. w.c.) ÷ (TEL ÷ 100)
With the friction rate and the required CFM for each duct segment, you enter the friction rate chart (also called a duct slide rule or Moody-based chart) and read off the duct diameter for round duct, or use the equivalent diameter tables to select rectangular dimensions.
A friction rate chart plots CFM on one axis and friction rate on another, with duct diameter as a family of curves. To size a duct segment:
1. Locate the design friction rate on the horizontal axis.
2. Move vertically to the CFM carried by that segment.
3. Read the nearest standard duct diameter. Always round up to the next standard size (e.g., from 5.8 in. to 6 in.) to stay within the pressure budget.
For rectangular duct, find a combination of width and height whose equivalent diameter matches the round size. Manual D provides tables for this conversion. Keep aspect ratios at or below 4:1 where possible to limit friction losses.
A trunk duct (also called a main or plenum extension) carries air from the air handler toward the zones it serves. Its CFM equals the sum of all branch CFMs it feeds. Trunk CFM decreases at each branch takeoff, so a reducing trunk gets smaller as it moves away from the unit.
A branch duct serves a single room or terminal. Its CFM equals the room CFM calculated in Step 1.
Size each trunk segment using the CFM it carries at that point in the system, always at the design friction rate.
For each duct segment, record: segment label, CFM carried, friction rate used, calculated diameter (round), and selected standard size or rectangular equivalent. A simple single-line duct layout sketch — a schematic, not a to-scale drawing — shows how segments connect and makes it easy for an inspector or colleague to follow your logic.
Duct sizing is a design activity, but duct installation involves real hazards. When you move from calculation to installation:
On the calculation side, always base your duct design on a completed Manual J report and a confirmed equipment selection. Sizing ducts for the wrong load or wrong airflow produces a system that will underperform, cause comfort complaints, and may contribute to moisture and indoor air quality problems.
Answer each question, then check it. Nothing is recorded; this is your own practice.