BLD-HVAC07-04 · Lesson 6 · 12 clock hours · demo
Metering Devices in Heat Pumps: TXVs, Check Valves, and Bi-Flow Devices
Objective. The student will explain how refrigerant metering changes between heating and cooling modes in a heat pump and correctly identify TXV, bi-flow TXV, check valve, and fixed-orifice metering devices on actual components and diagrams.
How Heat Pumps Meter Refrigerant
A heat pump must move heat in two directions—out of a building in cooling mode and into a building in heating mode. Because the indoor and outdoor coils swap roles when the reversing valve shifts, the refrigerant flow path reverses. That reversal creates a fundamental challenge: a metering device sized and oriented for one direction of flow will not meter correctly in the opposite direction. Understanding how the industry solves this problem is the core skill of this lesson.
The Job of a Metering Device
Every refrigeration circuit needs a metering device between the high-pressure liquid line and the low-pressure evaporator. Its job is to drop refrigerant pressure sharply and control how much liquid enters the evaporator. Too much liquid and the compressor floods; too little and the evaporator runs inefficiently. In a heat pump the metering device must do this job regardless of which coil is acting as the evaporator.
Thermostatic Expansion Valves (TXVs)
A TXV meters refrigerant by sensing the temperature and pressure at the evaporator outlet and adjusting a needle against a seat to hold a set superheat. The sensing bulb is clamped to the suction line near the evaporator outlet and is charged with a fluid that matches or is similar to the system refrigerant. When superheat rises the bulb pressure rises, pushing the needle open. When superheat falls the spring force and evaporator pressure push it closed. The external equalizer port connects to the suction line downstream of the bulb so the valve can account for pressure drop across the evaporator coil.
A standard TXV is designed for refrigerant flow in one direction only. Installed backward, the check ball inside or the valve geometry will block or mis-meter flow.
Bi-Flow TXVs
A bi-flow TXV (also called a bi-directional TXV) is designed so refrigerant can enter from either end and still receive proper metering. Internally, the valve has two inlet ports and an internal check arrangement that routes flow through the needle-and-seat assembly regardless of which end refrigerant enters. A single sensing bulb and equalizer port still control superheat. The practical advantage is that one bi-flow TXV on each coil replaces the combination of a standard TXV plus a check valve that would otherwise be needed to bypass the TXV when flow reverses.
When you sketch a bi-flow TXV, label the same parts as a standard TXV—sensing bulb, equalizer port, needle and seat, spring—and note that both inlet ports are present.
Check Valves in Heat Pump Circuits
A check valve allows refrigerant to flow freely in one direction and blocks it in the opposite direction. In a dual-TXV metering circuit, check valves are paired with each standard TXV so that in one mode refrigerant flows through the TXV and meters normally, while in the other mode refrigerant bypasses that TXV through the check valve and is metered by the TXV on the other coil instead.
Trace this logic for a system with TXV-A at the outdoor coil and TXV-B at the indoor coil:
- Cooling mode: High-pressure liquid travels from the condenser (outdoor coil) toward the indoor coil. TXV-B meters the flow; its paired check valve is closed. The check valve bypassing TXV-A is open, so liquid passes around TXV-A freely.
- Heating mode: Flow reverses. TXV-A meters the flow into the outdoor coil acting as evaporator; its paired check valve is closed. The check valve bypassing TXV-B is open, so liquid passes around TXV-B freely.
At any given moment, exactly one TXV is active and one is bypassed.
Fixed-Orifice Metering Devices
Some heat pump systems use a fixed orifice—commonly a piston-type device or a short capillary tube—instead of TXVs. These devices have no moving parts and meter in both directions without a check valve arrangement. Their simplicity reduces cost and service calls, but they cannot adjust to changing load or refrigerant charge conditions the way a TXV can. Many manufacturers use a fixed orifice on one coil and a TXV on the other, or a bi-flow TXV on each coil.
Reading a Dual-Metering Circuit Diagram
When you trace a heat pump metering circuit, use these steps:
1. Identify the mode (heating or cooling) and find which coil is the condenser and which is the evaporator.
2. Follow high-pressure liquid from the condenser outlet.
3. Determine which check valve is forward-biased (open) and which is reverse-biased (closed).
4. Identify which TXV is in the active flow path.
5. Follow low-pressure refrigerant from the active TXV outlet to the evaporator.
Practice this trace in both modes until it is automatic before the bench exercise.
Safety Notes
Before handling any refrigerant circuit components:
- PPE: Wear safety glasses and refrigerant-rated gloves. Liquid refrigerant and flashing refrigerant can cause frostbite and eye injury.
- Lockout/Tagout (LOTO): On any energized or pressurized system, follow your facility's lockout/tagout procedure before opening refrigerant circuits. Even bench components from a system may be under residual pressure—treat all valves and lines as pressurized until verified otherwise.
- Refrigerant handling: Only EPA Section 608 Universal certified technicians may purchase and handle regulated refrigerants. Do not vent refrigerants to atmosphere; use an approved recovery machine.
- Pressure gauges: Inspect gauge hoses for cracks before connecting. Stand to the side, not directly in line with fittings, when pressurizing.
- Cut-away components: Cut-away valves have sharp metal edges. Handle with care and keep fingers away from internal ports.
Key terms9
Metering deviceA component that restricts refrigerant flow between the high-pressure and low-pressure sides of a refrigerant circuit, dropping pressure and controlling how much liquid enters the evaporator.
Thermostatic expansion valve (TXV)A self-regulating metering device that uses a sensing bulb, spring, and equalizer port to maintain a set superheat at the evaporator outlet by modulating a needle against a seat.
Bi-flow TXVA thermostatic expansion valve designed to meter refrigerant flow correctly in either direction through the valve, making it suitable for heat pump applications without a bypass check valve.
Sensing bulbA fluid-filled tube clamped to the suction line that senses evaporator outlet temperature and transmits a pressure signal to the TXV diaphragm to open or close the valve.
External equalizer portA small connection on a TXV that pipes suction pressure from downstream of the sensing bulb to the underside of the diaphragm, compensating for pressure drop across the evaporator coil.
Check valveA one-way valve that allows refrigerant to flow freely in one direction and blocks flow in the reverse direction; used in dual-TXV heat pump circuits to bypass the inactive metering device.
Fixed orifice (piston)A metering device with no moving parts—typically a calibrated hole in a piston cartridge—that restricts flow in both directions without check valves; simpler but less adaptive than a TXV.
SuperheatThe temperature increase of refrigerant vapor above its saturation (boiling) temperature at the same pressure; the TXV regulates refrigerant flow to maintain a target superheat at the evaporator outlet.
Dual-metering circuitA heat pump refrigerant circuit arrangement that places a separate metering device (TXV or fixed orifice) at each coil, with check valves arranged so only the correct device is active in each operating mode.
In class: Instructor disassembles a TXV and bi-flow TXV on the bench; students sketch both and label sensing bulb, equalizer port, needle and seat, and spring; instructor explains how the bi-flow valve allows refrigerant in both directions. · Students trace refrigerant flow on a dual-metering-device circuit diagram (one TXV per coil with check valves) in both heating and cooling modes, noting which metering device is active and which is bypassed in each mode. · Bench exercise: using a hand valve and pressure gauge, students open and close check valves to simulate mode switching and observe pressure differential, then record observations and answer analysis questions on the lab sheet.
Materials: Disassembled TXV and bi-flow TXV (cut-away or serviceable units), check valves, dual-metering circuit diagram, hand valves, pressure gauges, lab sheets, ASHRAE Fundamentals chapter on expansion devices
Check: Students correctly label all components on a blank diagram and answer three analysis questions about metering device function in each mode; pass mark 80%.
Practice check8