BLD-HVAC07-02 · Lesson 4 · 12 clock hours · theory

Pressure-Temperature Relationships and PT Chart Use

Objective. Students will use a standard refrigerant pressure-temperature (PT) chart to determine saturation temperature from a given gauge pressure and vice versa for at least four common refrigerants.

What Is the Pressure-Temperature Relationship?

Every refrigerant has a predictable relationship between its pressure and its temperature when it is in a saturated state — that is, when liquid and vapor exist together at the same time inside a container or component. At saturation, if you know the pressure, you automatically know the temperature, and vice versa. This is not a coincidence; it is a physical law that applies to all pure refrigerants and many blends.

When a refrigerant is saturated, raising the pressure raises the saturation temperature. Lowering the pressure lowers the saturation temperature. This principle is what makes the refrigeration cycle work: the system deliberately creates low pressure on the suction side so the refrigerant boils (evaporates) at a cold temperature and absorbs heat from the space being cooled, then raises pressure on the discharge side so the refrigerant condenses at a warm temperature and rejects that heat outdoors.

The Pressure-Temperature (PT) Chart

A PT chart is a published reference table that lists saturation pressures and corresponding saturation temperatures for specific refrigerants. Technicians use it constantly — on startup, during charging, when diagnosing a problem, and when verifying normal operation.

PT charts are printed on laminated pocket cards, included in service manuals, and built into digital apps on phones and tablets. No matter the format, they all contain the same core data for each refrigerant: a column of temperatures (usually in °F) paired with a column of pressures (usually in psig — pounds per square inch gauge).

Gauge pressure (psig) is what your manifold gauge reads in the field. It is absolute pressure minus atmospheric pressure (approximately 14.7 psi at sea level). PT charts are formatted in psig because that is what technicians measure directly.

Common Refrigerants You Will Look Up

Each refrigerant has its own column or its own separate PT chart. Never cross-reference the wrong refrigerant column — pressures at any given temperature differ significantly between refrigerants, and using the wrong data will lead to incorrect diagnosis and possible equipment damage.

How to Read a PT Chart: Psig to °F

1. Locate the correct refrigerant section of the chart.

2. Find your gauge pressure reading in the pressure column.

3. Read across to the corresponding temperature column — that is the saturation temperature at that pressure.

This tells you what temperature the refrigerant should be changing state (boiling or condensing) at that pressure. On the low side, this is the evaporator saturation temperature. On the high side, this is the condensing saturation temperature.

How to Read a PT Chart: °F to Psig

1. Locate the correct refrigerant section.

2. Find the target temperature in the temperature column.

3. Read across to the pressure column — that is the pressure you would expect at that saturation condition.

This direction is used when you know the design conditions (for example, a 40 °F evaporator target) and need to know what suction pressure to expect.

Superheat and Subcooling: Why Saturation Matters

Saturation temperature is the baseline for two key measurements technicians make on every service call:

You cannot calculate either value without first finding saturation temperature from the PT chart.

Safety Notes

Key terms8

SaturationThe condition in which a refrigerant exists as a mixture of liquid and vapor at a specific pressure and temperature simultaneously; the state where pressure and temperature are directly linked.
PT Chart (Pressure-Temperature Chart)A reference table listing the saturation pressure and corresponding saturation temperature for a specific refrigerant; used for diagnosis and charging.
Psig (Pounds per Square Inch Gauge)Pressure measured relative to atmospheric pressure, as displayed on a standard manifold gauge; PT charts are expressed in psig for field use.
Evaporator Saturation TemperatureThe temperature at which the refrigerant boils (changes from liquid to vapor) in the evaporator, determined by reading the low-side gauge pressure on the PT chart.
Condensing Saturation TemperatureThe temperature at which the refrigerant condenses (changes from vapor to liquid) in the condenser, determined by reading the high-side gauge pressure on the PT chart.
SuperheatThe number of degrees Fahrenheit the refrigerant vapor is above its saturation temperature at a given pressure; measured at the suction line to confirm the evaporator is feeding properly.
SubcoolingThe number of degrees Fahrenheit the liquid refrigerant is below its saturation temperature at a given pressure; measured at the liquid line to confirm the condenser has fully condensed the refrigerant.
Gauge PressurePressure read directly by a gauge, equal to absolute pressure minus local atmospheric pressure (approximately 14.7 psi at sea level).

Worked examples4

1. A technician measures a suction-side gauge pressure of 68 psig on an R-22 system. What is the evaporator saturation temperature?
  1. Step 1: Locate the R-22 section of the PT chart.
  2. Step 2: Find 68 psig in the pressure column for R-22.
  3. Step 3: Read across to the temperature column.
Answer: Approximately 40 °F. At 68 psig, R-22 has a saturation temperature of about 40 °F, which is a typical design evaporator condition for air conditioning.
2. A technician is working on an R-410A residential air conditioner. The low-side gauge reads 118 psig. What is the evaporator saturation temperature?
  1. Step 1: Locate the R-410A section of the PT chart — note that R-410A operates at much higher pressures than R-22.
  2. Step 2: Find 118 psig in the R-410A pressure column.
  3. Step 3: Read across to the temperature column.
Answer: Approximately 40 °F. R-410A requires roughly 118 psig to achieve a 40 °F saturation temperature, compared to about 68 psig for R-22 at the same temperature.
3. A technician needs to verify subcooling on an R-404A walk-in cooler. The high-side gauge reads 225 psig, and the liquid-line temperature measured with a clamp thermometer is 90 °F. What is the subcooling?
  1. Step 1: Locate the R-404A section of the PT chart.
  2. Step 2: Find 225 psig in the R-404A pressure column and read the corresponding saturation temperature — approximately 105 °F.
  3. Step 3: Subtract the actual liquid-line temperature from the saturation temperature: 105 °F − 90 °F = 15 °F subcooling.
Answer: 15 °F subcooling. This indicates the liquid refrigerant has cooled 15 degrees below its condensing saturation temperature, confirming full condensation with margin.
4. A system design calls for a 45 °F evaporator saturation temperature using R-134a. What suction pressure should the technician expect to see on the low-side gauge?
  1. Step 1: Locate the R-134a section of the PT chart.
  2. Step 2: Find 45 °F in the temperature column for R-134a.
  3. Step 3: Read across to the corresponding pressure column.
Answer: Approximately 46 psig. R-134a at 45 °F saturation corresponds to roughly 46 psig on the low-side gauge, giving the technician a target suction pressure for this design condition.
In class: Instructor demonstrates PT chart lookup for three refrigerants using a physical laminated chart and a digital PT chart app; students follow along and record answers. · Timed PT chart drill: students complete 20 lookup exercises (psig to °F and °F to psig) for R-22, R-410A, R-134a, and R-404A using a physical chart only, scored for accuracy and speed. · Real-world scenario exercise: instructor calls out operating pressures from a fictional job ticket; students use the PT chart to determine if the system is operating within normal saturation temperature ranges.
Materials: Laminated refrigerant PT charts, PT chart drill worksheets, digital PT chart application on instructor tablet for comparison, job ticket scenario handouts, calculators
Check: Drill worksheet scored: students must achieve at least 80% accuracy (16 of 20 correct). Instructor observes each student performing at least two unaided PT chart lookups during the scenario exercise.

Practice check8

Answer each question, then check it. Nothing is recorded; this is your own practice.

Refrigeration fundamentals / EPA 608 core knowledge
1. What physical condition must a refrigerant be in for the PT chart relationship to apply directly?
NATE Core — Refrigeration / HVAC Excellence
2. A technician reads 68 psig on the low-side gauge of an R-22 system. According to a standard PT chart, the evaporator saturation temperature is approximately:
NATE Core — Refrigeration fundamentals
3. Why does R-410A require a higher suction pressure than R-22 to achieve the same evaporator saturation temperature?
NATE Core — Air Conditioning / HVAC Excellence
4. A technician measures a suction-line temperature of 55 °F and the PT chart shows the saturation temperature at the measured suction pressure is 40 °F. What is the superheat?
EPA 608 / NATE Core — Refrigerants
5. A technician uses an R-22 PT chart column while diagnosing an R-410A system. What is the most likely result?
NATE Core — Air Conditioning / HVAC Excellence
6. Which of the following best describes subcooling?
EPA 608 — Regulations and environmental impact
7. Under Section 608 of the Clean Air Act, a technician who vents refrigerant intentionally to the atmosphere is:
NATE Core — Safety / NCCER HVAC — Tools and safety
8. A technician is preparing to connect manifold gauges to a system containing R-410A. Which safety precaution is most important given R-410A's pressure characteristics?