TEC-DATA82-06 · Lesson 3 · 12 clock hours · lab

BIOS/UEFI Configuration and Out-of-Band Management

Objective. Students will configure BIOS/UEFI settings—boot order, secure boot state, memory operating speed, and IPMI/iDRAC/iLO network address—and demonstrate remote server power control from a management workstation.

⚠ Pending professional review

This lesson, its worked examples and its practice questions has not yet been verified by an industry-certified professional or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.

VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.

BIOS/UEFI Configuration and Out-of-Band Management

What BIOS and UEFI Do

Every server contains firmware that runs before the operating system loads. The older standard is BIOS (Basic Input/Output System); the modern replacement is UEFI (Unified Extensible Firmware Interface). UEFI supports drives larger than 2 TB, faster boot times, Secure Boot, and a graphical setup interface. In a data center you will encounter both, but new servers ship with UEFI by default. Regardless of which firmware a server uses, it is your entry point for hardware-level configuration that the OS cannot change.

Key Settings You Will Configure

Boot device priority tells the server which device to try first when starting: typically the primary SSD or hard drive array, followed by the network (PXE boot), then optical or USB. Set PXE boot last unless you are deliberately deploying an OS over the network, because an accidental network boot can stall a production server.

UEFI vs. Legacy (CSM) mode controls how the firmware hands off to the OS loader. Keep servers in UEFI mode unless the OS or hardware explicitly requires legacy mode; Secure Boot only works in UEFI mode.

Secure Boot validates that the OS bootloader is signed by a trusted authority before executing it. Enable Secure Boot on servers running supported OS versions to protect against bootkits and unauthorized code at startup.

Memory operating speed (DRAM frequency) is usually set to "Auto," which lets the firmware negotiate the highest speed the installed DIMMs and CPU memory controller support. A spec sheet may require you to set a specific speed for workload predictability or hardware qualification. Never set a speed higher than the DIMM's rated speed.

Unused onboard ports (unused SATA controllers, serial ports, embedded video when a PCIe GPU is present) should be disabled to reduce attack surface and free interrupt resources. Always document what you disable so the next technician knows the state.

Out-of-Band Management: IPMI, iDRAC, and iLO

Out-of-band (OOB) management lets you access a server's power controls, hardware sensors, and a virtual console even when the main OS is crashed, the server is powered off, or you are physically in a different building. It runs on a dedicated management controller with its own processor, memory, and network port—completely separate from the server's main CPUs and data NICs.

For OOB management to work, the management port must have a valid IP address, subnet mask, and default gateway on a dedicated management VLAN—separate from production traffic. You configure this address either inside the BIOS/UEFI setup screens or through the BMC's own setup utility (often reached during POST by pressing a key combination shown on screen).

Navigating the Web Interface

Once the management IP is set and your workstation is on the same management network, open a browser, type the IP address, and log in with the administrator credentials. Inside the iDRAC or iLO interface you will find:

Remote Power Cycle Procedure

A remote power cycle is a routine task for a data center technician. The correct sequence is: (1) verify you are connected to the correct server by checking the service tag displayed in the management interface against the physical label; (2) attempt a graceful shutdown first unless the server is unresponsive; (3) confirm the physical power LEDs show the server is off before initiating power-on; (4) document the time, interface used, and reason in your configuration record.

Safety Considerations

Out-of-band management gives you the ability to cut power to a running server from across the room or across the country. Always confirm server identity before issuing any power command—a mistaken force-off on the wrong server can cause unplanned downtime and data loss. When physically working inside a server, follow lockout/tagout (LOTO) procedures: power down through the OS, then cut power at the PDU breaker and apply your lock before opening the chassis. OOB management does not eliminate the need for LOTO—the BMC still has standby power even when the server appears off. Wear an ESD wrist strap or use an ESD mat when handling circuit boards and DIMMs. Do not modify BIOS settings on a production server without a change-management approval and a rollback plan.

Key terms10

UEFI (Unified Extensible Firmware Interface)Modern server firmware standard that replaces legacy BIOS; supports drives larger than 2 TB, Secure Boot, and faster startup initialization.
Secure BootA UEFI feature that checks the digital signature of the OS bootloader before execution to prevent unauthorized or malicious code from running at startup.
IPMI (Intelligent Platform Management Interface)An open industry standard protocol that defines communication between management software and a server's Baseboard Management Controller for out-of-band hardware monitoring and control.
BMC (Baseboard Management Controller)A dedicated microcontroller embedded on the server motherboard that runs independently of the main CPU and OS, providing out-of-band management functions including power control and sensor monitoring.
iDRAC (Integrated Dell Remote Access Controller)Dell's proprietary out-of-band management implementation; provides a web interface, SSH access, virtual console, power control, and system event log for Dell servers.
iLO (Integrated Lights-Out)HPE's proprietary out-of-band management system that offers the same categories of functionality as iDRAC for HPE ProLiant servers.
System Event Log (SEL)A timestamped hardware-level log maintained by the BMC that records events such as temperature alerts, fan failures, power supply faults, and memory errors.
Out-of-Band (OOB) ManagementServer administration carried out over a dedicated management network and controller that operates independently of the server's main OS and data network interfaces.
PXE Boot (Preboot Execution Environment)A method of booting a server by loading an OS image from a network server rather than a local disk; used for OS deployment but should be low priority in production boot order.
Lockout/Tagout (LOTO)An OSHA-required safety procedure that physically locks and labels energy-isolating devices to prevent unexpected re-energization while a technician is working on equipment.
In class: Instructor demo: navigate Dell iDRAC or HPE iLO web interface; show virtual console, power control, and system event log—students follow on their assigned server. · Students configure BIOS settings per a written specification sheet (e.g., set boot device priority, disable unused onboard ports, confirm UEFI mode), save settings, and document each changed parameter on a configuration record form. · Partner exercise: one student remotely powers off and powers on a partner's server through the out-of-band management interface while the partner watches the physical server; they swap roles and record timestamps and interface steps.
Materials: Servers with iDRAC/iLO/IPMI configured, management workstations on a dedicated out-of-band network, configuration record forms, CompTIA Server+ objectives (server management domain), manufacturer BIOS/iDRAC user guide
Check: Configuration record form matches instructor-provided spec sheet with no deviations; remote power cycle successfully demonstrated and documented—pass requires both.

Practice check8

Answer each question, then check it. Nothing is recorded; this is your own practice.

CompTIA Server+ — Server Management
1. A technician needs to boot a server from its SAN-attached drive array under normal production conditions. Which boot device priority order is most appropriate?
CompTIA Server+ — Server Management
2. Secure Boot on a server requires which firmware mode to function?
OSHA 10 — Hazard Recognition and Control
3. A technician is preparing to swap a failed DIMM inside a powered-down server. The server is managed via iDRAC. What must the technician do before opening the chassis?
CNet CDCTP — Data Center Operations
4. Which component allows a technician to view the server's screen and control the keyboard remotely through the iDRAC interface?
CompTIA Server+ — Server Management
5. Before issuing a remote force power-off command through iDRAC, what is the most important verification step a technician should perform?
CompTIA Server+ — Server Management
6. A server's System Event Log shows repeated correctable memory error entries for DIMM slot A2 over the past 48 hours. What is the best immediate action?
CNet CDCTP — Data Center Security and Operations
7. What is the primary reason an out-of-band management port should be placed on a dedicated management VLAN separate from production traffic?
CompTIA Server+ — Server Hardware
8. A technician sets memory operating speed in UEFI to a value higher than the installed DIMMs' rated speed. What is the most likely result?