Objective. Students will explain the code requirements for Phase I and Phase II firefighters' emergency operation and for emergency power operation, and correctly operate a training elevator through a Phase I recall and Phase II manual operation sequence.
This lesson, its worked examples and its practice questions has not yet been verified by a licensed professional engineer or master tradesperson or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.
VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.
Fire departments depend on elevator systems to move personnel and equipment quickly to upper floors. ASME A17.1 Safety Code for Elevators and Escalators establishes the exact requirements for firefighters' emergency operation so that every elevator in the country behaves the same way when a firefighter turns the key. As a pre-apprentice, you must know these requirements cold — both for the credential exams and because a mis-wired or mis-programmed firefighters' service can cost lives.
---
Phase I removes the elevator from normal passenger service and returns it to a designated landing where firefighters can take control.
What triggers Phase I?
Phase I is initiated by either of two inputs:
Switch location and key type. The Phase I key switch must be located in the lobby at the designated landing — in most installations this is the main entry floor or the floor designated by the authority having jurisdiction (AHJ). The code specifies a standard key so that fire departments across the country carry one key that works in every building. This key is commonly called the FEO-K1 key, though you should always verify the key type specified for the installation you are working on.
What the car must do during Phase I:
1. The car stops at the next available floor if traveling away from the designated landing (it does not stop immediately mid-run if the doors are closed and the car is moving).
2. The car does not respond to landing calls or car calls.
3. The car travels to the designated landing, doors open fully, and the car remains parked with doors open.
4. The car stays out of service until Phase I is cancelled.
BYPASS position. If a particular lobby has an activated smoke detector that is faulty or in an area of known fire, the BYPASS position allows that floor's detector to be ignored so the elevator does not land on that floor. The car still recalls under signals from other detectors.
Multiple cars. In a group of elevators, all cars in the group must respond to Phase I simultaneously when a lobby detector activates. Each car has its own recall sequence.
---
Phase II gives a firefighter inside the car full manual control. The passenger control system is locked out; only the firefighter's key controls the car.
Initiating Phase II. A three-position key switch inside the car — marked OFF / HOLD / ON — must be turned to ON. This switch is typically located on the car operating panel.
Door behavior under Phase II:
HOLD position. Turning the Phase II switch to HOLD keeps the car at the current landing with doors open. This is used when the firefighter needs to load equipment without the car traveling.
Car lighting. The code requires that the car have emergency lighting that activates automatically if normal car lighting power fails. The minimum illumination level must meet the code requirement so firefighters can operate in the car even if building power is disrupted.
Returning to normal service. Phase II ends when the key switch is turned to OFF. Phase I ends when the lobby switch is turned to OFF (and any automatic detector signals have cleared). Both must be reset before the elevator returns to passenger service.
---
When normal building power fails, some elevators are connected to an emergency generator. ASME A17.1 requires that when the building switches to emergency power, elevators return cars to the designated landing one at a time (to avoid overloading the generator) and open their doors so passengers are not trapped. This is sometimes called automatic emergency terminal stopping or emergency power recall. Only a limited number of cars — as determined by available generator capacity — may be kept in service on emergency power. The AHJ and building owner designate which cars remain operable.
---
---
When you study ASME A17.1 sections covering firefighters' emergency operation, separate the requirements into two categories:
1. Physical equipment requirements — switch location, key type, car lighting, door equipment.
2. Sequence-of-operation requirements — what the car must do, in what order, when Phase I or Phase II is activated.
This habit helps you write accurate deficiency reports and will serve you well on both the NEIEP/IUEC and NAEC CET credential exams.