Objective. Students will correctly trace the current path through a multi-rung relay ladder diagram, predict which output coils energize under a given set of input conditions, and verify their predictions on a demonstration relay panel.
This lesson, its worked examples and its practice questions has not yet been verified by a licensed professional engineer or master tradesperson or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.
VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.
A relay is an electrically operated switch. When current flows through its coil, a magnetic field pulls a set of contacts to change position. Contacts that are open when the coil is de-energized are called normally-open (NO); contacts that are closed when the coil is de-energized are called normally-closed (NC). When the coil energizes, NO contacts close and NC contacts open — this action is called picking up the relay. When the coil loses power, contacts return to their resting state — the relay drops out.
Elevator controllers have used relay logic for decades. Even modern microprocessor-based systems include relay output stages, and technicians must be able to read legacy relay circuits during maintenance, troubleshooting, and modernization work. Understanding relay logic is foundational to every credential in this trade.
A ladder diagram is a standardized schematic that represents relay logic in a format that mirrors the rungs of a ladder. Two vertical lines called rails carry the supply voltage — typically the left rail is the line (L1) side and the right rail is the neutral or return (L2) side. Horizontal lines between the rails are rungs. Each rung contains one or more contact symbols in series or parallel, and ends at an output element such as a relay coil or an indicator lamp.
Contact symbols follow a simple visual convention:
Relays are usually labeled with a letter-number code such as 1CR, 2CR, 3CR (CR = control relay). The same label appears on the coil symbol and on every contact belonging to that relay anywhere in the diagram. This is critical: when coil 2CR energizes, every contact labeled 2CR in the entire diagram changes state simultaneously.
To determine whether an output coil energizes, trace a continuous path from the left rail to the right rail through that rung. Apply these rules:
1. A normally-open contact conducts only when its relay coil is energized (contact closed).
2. A normally-closed contact conducts only when its relay coil is de-energized (contact closed in rest state).
3. Contacts in series all must conduct for current to reach the coil.
4. Contacts in parallel provide alternate paths — any one conducting path is enough.
Work left to right, rung by rung. Mark each contact as conducting (circle it) or blocking (cross it) based on the known input conditions. If an unbroken path exists from L1 to L2 through the rung, the output coil energizes.
A common relay logic pattern in elevator control is the seal-in circuit. A momentary push-button (NO contact) is placed in series with a coil. A NO contact of that same relay is wired in parallel with the push-button. When the button is pressed, the coil picks up; its own contact closes and holds the coil energized even after the button is released. To drop the relay out, a NC contact — typically operated by another relay or a safety device — must open the rung. Seal-in circuits appear in hall-call registration, car-call registration, and floor-leveling logic.
With multiple rungs, the state of one relay directly affects other rungs. Work systematically:
1. Identify all external inputs (push-buttons, limit switches, selector contacts) and note which are energized or activated.
2. Start at Rung 1 and determine whether the output coil energizes.
3. Record the new coil state and update any contacts carrying that relay's label in later rungs.
4. Continue rung by rung until all outputs are resolved.
5. Check for inter-rung feedback: a coil energized on rung 3 may close a contact that feeds rung 2. Re-evaluate if needed.
Always re-check from the top after any coil state changes until no further changes occur — this is called reaching a stable state.
Control voltage does not mean low hazard. Elevator controller circuits commonly operate at 115 V AC or higher for coil circuits. Before working inside a controller cabinet:
On the demonstration panel used in today's activity, the supply is low-voltage DC and current is limited — it is safe for hands-on learning. Real elevator controllers are not demonstration panels; treat them with full electrical safety discipline on the job.
Professional technicians develop a habit of scanning the diagram vertically by relay label before tracing rungs. Find coil 3CR, then locate every 3CR contact in the diagram and note which rungs they affect. This preview prevents missed contacts during troubleshooting. Pair this vertical scan with a left-to-right rung trace and you will rarely miss an interaction.
Answer each question, then check it. Nothing is recorded; this is your own practice.