Objective. Students will interpret a multi-page PLC control drawing set and produce a correctly formatted one-page I/O wiring diagram and address table for a simple control application.
Every PLC installation produces paperwork as important as the wiring itself. When a motor fails at 2 a.m., the technician on call must trace the fault quickly. Without accurate drawings, that job becomes dangerous guesswork. Precise, standardized documentation protects workers, speeds troubleshooting, and is required by the National Electrical Code (NEC) and most facility standards. As an electrician working on PLC-controlled systems, you must be able to read the documentation others created and produce documentation that others can rely on.
A complete PLC control drawing set typically contains several coordinated sheets. Understanding each page is the first step toward reading the whole set.
Title Block — Found in the lower-right corner of every sheet, the title block records the project name, drawing number, revision level, date, and the name of the person who drew and checked the sheet. Always confirm you are reading the current revision before using any drawing for work.
I/O Wiring Diagram — This is the central document for the electrician. It shows every physical wire connection between field devices (sensors, switches, pushbuttons) and the PLC input and output terminals. Each terminal is labeled with its address and a wire number. Input devices appear on the left side of the PLC module; output devices (contactors, indicator lights, solenoids) appear on the right.
Terminal Strip Schedule — A table listing every terminal block on a panel, its terminal number, the wire connected to it, and where that wire goes. It acts as a map between the I/O diagram and the physical panel.
Address Table (I/O Address List) — A spreadsheet-style table assigning a unique PLC address to every input and output. A typical entry includes the address tag (for example, I:0/0 or X0 depending on PLC brand), a plain-language description ("Start Pushbutton"), the device type, and the terminal number. This table is the bridge between the wiring diagram and the PLC program.
The National Electrical Manufacturers Association (NEMA) and IEEE publish standard schematic symbols. Using recognized symbols ensures that any qualified electrician can read your drawing without special training. Common symbols used in PLC I/O diagrams include:
Wire numbers are assigned sequentially or by system (DC common wires may carry a designated number such as 0 V COM). Every wire segment that connects two unique points gets a unique number; segments that are electrically the same point share one number.
To create a compliant drawing for a simple application, follow these steps:
1. Define the application. List every input and output device before drawing anything. For a pump control system with one start pushbutton, one float switch (high-level shutdown), and one motor contactor, you have two inputs and one output.
2. Assign addresses. Use the PLC manufacturer's addressing format consistently. Input 1 might be I:0/0, Input 2 might be I:0/1, and Output 1 might be O:0/0. Record these in your address table first.
3. Draw the PLC module outline. A rectangle represents the module. Label input terminals on the left and output terminals on the right. Show the common (COM) terminal and the DC or AC supply connections.
4. Add field devices. Draw each input device using the correct NEMA symbol, connected by a line to its input terminal. Draw each output device connected to its output terminal. Route wires to terminal blocks before they leave the panel, and number each wire segment.
5. Label everything. Every device gets a tag (PB1, FS1, M1). Every terminal gets its number. Every address is noted next to its terminal. The PLC module itself is labeled with its model reference.
6. Complete the title block. Fill in the project name, drawing number, revision (start at Rev. 0 or A), your name, and the date. A drawing without a complete title block is not finished.
PLC panels operate at voltages that can cause electrocution and arc flash. The following safety practices apply every time you work on or near control panels:
When reviewing someone else's drawing, work through a checklist systematically: title block complete, revision current, all addresses matching the address table, correct NEMA symbols, wire numbers present on every segment, and COM connections shown. Written peer review comments should be specific ("Wire between PB1 and terminal 3 has no wire number") rather than general ("labeling is wrong"). Clear documentation is a professional obligation in this trade.
Answer each question, then check it. Nothing is recorded; this is your own practice.