Objective. Learners will demonstrate a complete six-step OSHA-compliant lockout/tagout procedure on a training panel and perform hands-only CPR and AED use to the standard required for a nationally recognized CPR/AED/First Aid certification.
Electricity kills silently and instantly. A worker who contacts an energized conductor at 120 V can suffer cardiac arrest in under a second. OSHA's Lockout/Tagout (LOTO) standard — 29 CFR 1910.147 — exists for exactly this reason: it requires a written, step-by-step procedure that removes hazardous energy from equipment before anyone works on it. Knowing LOTO is not optional for an electrician; it is a legal requirement on every job site.
OSHA 10 training and NCCER curricula both treat LOTO and emergency response as foundational skills. Employers screen for them before a worker ever touches a panel.
Memorize these steps in order. Skipping any single step can result in a fatal exposure.
Step 1 — Notify affected employees.
Tell everyone who operates or works near the equipment that it will be shut down and locked out. This prevents a co-worker from accidentally re-energizing the circuit while you work.
Step 2 — Shut down the equipment.
Use the normal stopping procedure for the machine or circuit. Press the stop button, flip the switch, or use whatever control the manufacturer specifies. The equipment must reach a complete stop before you proceed.
Step 3 — Isolate the energy source.
Operate the energy-isolating device — typically a disconnect switch or breaker — to physically separate the equipment from its energy source. Do not rely on a control switch alone; it is not an energy-isolating device.
Step 4 — Apply a lockout device and tag.
Place your personal lock on the hasp of the energy-isolating device so that it cannot be re-energized without your key. Attach a tag that identifies you, the date, and the reason for the lockout. Each authorized worker applies their own lock — never share a lock.
Step 5 — Release or restrain stored energy.
Capacitors hold charge. Springs hold tension. Gravity can drop a raised load. Bleed, block, drain, or restrain all stored energy before proceeding. In electrical work this commonly means discharging capacitors and verifying that gravity-operated equipment is blocked.
Step 6 — Verify zero energy state.
Attempt to start the equipment using its normal controls — it should not respond. Then use a properly rated and tested non-contact voltage tester or multi-meter to confirm that all conductors you will touch are at zero volts. Test the tester on a known live source before and after to confirm the tester itself is working. Only after this verification is it safe to begin work.
When work is complete, remove all tools and materials, restore guards, notify affected employees, remove your lock and tag, and return energy to the equipment in the reverse order.
Even during a lockout procedure, wear appropriate PPE: safety glasses, voltage-rated gloves when testing for zero energy, and arc-rated clothing if the task requires exposure to potential arc flash. The LOTO procedure reduces — but does not eliminate — all hazard during verification.
If a co-worker is in contact with an energized source, do not touch them. Your first action is to de-energize and lock out the circuit. Only after the power is confirmed off is it safe to approach the victim. Rushing in to pull someone free from a live conductor turns you into a second victim.
Call 9-1-1 immediately. Give dispatchers: your exact location (address, floor, room), the nature of the emergency (electrical shock), the number of victims, and whether the scene is safe.
After the circuit is de-energized and the scene is safe, begin assessment. If the victim is unresponsive and not breathing normally:
1. Call 9-1-1 or direct someone specific to call.
2. Begin chest compressions: place the heel of one hand on the center of the chest, place the other hand on top, press down at least 2 inches at a rate of 100–120 compressions per minute. Push hard and fast.
3. Continue until an AED arrives, a trained rescuer takes over, or EMS assumes care.
Hands-only CPR is appropriate for adult victims of sudden cardiac arrest. If you are trained in rescue breaths, use them; if not, compressions alone are far better than nothing.
Automatic External Defibrillators (AEDs) analyze heart rhythm and deliver a shock if one is needed. When the AED arrives:
1. Power it on.
2. Attach pads as shown in the diagram on the pads — one below the right collarbone, one on the left side below the armpit.
3. Ensure no one is touching the victim while the AED analyzes.
4. Follow the voice prompts: if a shock is advised, clear everyone, then press the shock button.
5. Immediately resume compressions after the shock.
Electrical burns often appear minor on the skin but damage tissue along the entire current path. Do not remove clothing stuck to a burn. Cover lightly with a clean, dry dressing and keep the victim warm until EMS arrives. For lacerations, wear nitrile gloves, apply firm direct pressure with a clean bandage, and maintain pressure until bleeding stops or EMS arrives. Do not remove a bandage that is soaked — add more material on top.
LOTO, CPR, AED use, and basic first aid are the emergency response triangle for electricians. LOTO prevents the emergency. CPR and AED use save a life when prevention has failed. Knowing both — and keeping your skills current with certified training — is a professional and legal obligation in this trade.