Objective. Students will perform a jar test to determine optimum coagulant dose for a turbid water sample, then explain how flocculation and sedimentation basin design parameters—including detention time and overflow rate—affect settled-water quality.
This lesson, its worked examples and its practice questions has not yet been verified by a licensed professional in the field or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.
VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.
Removing suspended particles from raw water is one of the most important steps in drinking water treatment. Three linked processes accomplish this: coagulation, flocculation, and sedimentation. Together they reduce turbidity, color, and many pathogens before water ever reaches a filter.
Most suspended particles in raw water—clay, silt, organic matter, and microorganisms—carry a negative surface charge. Because like charges repel, particles push each other apart and remain dispersed for a very long time. Gravity alone cannot settle them fast enough for practical treatment. Coagulation is the chemical step that overcomes this charge barrier.
A coagulant is a chemical added to the water to neutralize the negative surface charges on particles. The most common coagulant in water treatment is alum (aluminum sulfate). When alum dissolves in water it releases aluminum ions and reacts with the water's alkalinity to form aluminum hydroxide. This reaction consumes alkalinity and lowers pH, so operators must monitor pH closely. The optimal coagulation pH for alum is roughly 6.5–7.5, though the exact range depends on raw-water chemistry.
Coagulants are added at a rapid-mix (flash-mix) point—a zone of very intense turbulence that distributes the chemical throughout the flow within seconds. Inadequate mixing results in poor charge neutralization; excessive coagulant doses can re-stabilize particles (a phenomenon called restabilization) and worsen turbidity.
Because raw-water quality changes daily, operators cannot rely on a fixed coagulant dose. The jar test is a bench-scale procedure that mimics the full treatment train in miniature. Six jars are filled with identical raw-water samples and dosed with increasing amounts of coagulant. All jars receive the same rapid-mix period (high RPM), then a slow-mix flocculation period (low RPM), then a settling period with no mixing. After settling, operators measure the turbidity of each jar's supernatant. The dose that produces the lowest settled turbidity—while staying within dose limits—is the optimum dose.
Record every step: initial turbidity, dose volume, RPM settings, mixing times, and final turbidity. Plot dose on the x-axis and settled turbidity on the y-axis. The optimum dose corresponds to the lowest point on the curve.
After coagulation neutralizes surface charges, particles begin to collide and stick together. Flocculation provides gentle, sustained mixing to encourage those collisions and grow larger, heavier aggregates called floc. Too much mixing energy breaks floc apart; too little and particles do not collide often enough. Flocculator paddles or turbines rotate at low speed, usually measured in RPM or expressed as the velocity gradient G (units: s⁻¹). Operators adjust G to balance collision frequency with floc strength. Typical flocculation times range from 20 to 40 minutes, though design varies.
Settled water flows into a sedimentation basin (also called a clarifier) where velocity drops sharply and floc settles to the bottom as sludge. Two key design parameters describe basin performance:
Surface Overflow Rate (SOR) — also called surface loading rate — is the flow rate divided by the surface area of the basin:
> SOR = Flow (gal/day) ÷ Surface Area (ft²)
Typical SOR values for conventional clarifiers are roughly 500–1,000 gal/day/ft², though your operator reference manual provides ranges for your state's criteria. A lower SOR means more settling time per unit area and better particle removal.
Detention Time (DT) — also called hydraulic retention time (HRT) — is the theoretical time water spends in the basin:
> DT (hours) = Basin Volume (gal) ÷ Flow Rate (gal/hr)
Typical sedimentation detention times are approximately 2 to 8 hours for conventional basins. Longer detention time generally improves settleability but requires a larger basin.
Sludge that accumulates on the basin floor is removed by mechanical scrapers or by periodic draining and must be disposed of properly according to state and local regulations.
Personal Protective Equipment (PPE): Wear safety glasses and chemical-resistant gloves whenever handling alum solution or any coagulant chemical. A lab coat or chemical-resistant apron protects skin and clothing from spills.
Turbidimeter: Handle the glass sample cells carefully to avoid breakage. Broken glass is a laceration hazard—dispose of shards in a designated sharps or glass-waste container, never a regular trash can.
Alum: Alum solution is acidic. In the event of skin or eye contact, flush immediately with large amounts of water for at least 15 minutes and notify your instructor. Know the location of the eyewash station before you begin.
Housekeeping: Wipe up spills immediately. Wet floors are a slip hazard. Label all containers, even dilute solutions. Never pour chemicals back into stock bottles.
Bench-Scale Flocculator: Keep hands and loose clothing away from rotating paddle shafts. Secure long hair before operating motorized equipment.
The jar test is not just a classroom exercise—operators at full-scale plants run jar tests routinely whenever raw-water turbidity spikes after storms or when source water quality shifts. A properly run jar test can save thousands of dollars in chemical costs while maintaining water quality. Your ability to run a jar test, read a turbidimeter accurately, and calculate SOR and detention time are core competencies tested on both Class I and Class II water operator licensing exams.