BLD-PLUM06-11 · Lesson 3 · 18 clock hours · demo
ASSE Backflow Prevention Certification: Cross-Connection Control, Devices, and Field Testing Review
Objective. Students will describe cross-connection hazard categories, select the correct backflow prevention assembly for a given installation scenario, and explain the step-by-step field testing procedure for common assemblies as required by the ASSE backflow tester certification.
Why Backflow Prevention Matters
Potable water systems are designed to flow in one direction: from the supply main to the point of use. Backflow occurs when that flow reverses, drawing contaminated water back into the clean supply. Two conditions cause backflow: back-siphonage (a negative pressure in the supply line, such as during a water-main break) and backpressure (downstream pressure exceeds supply pressure, as with a boiler or pressurized irrigation system). Either condition can introduce biological, chemical, or physical contaminants into drinking water, making cross-connection control a public-health priority enforced by state plumbing codes and local water authorities.
Cross-Connection Hazard Classification
Before selecting any assembly, you must classify the hazard on the downstream side of the connection:
- Health hazard (high hazard): The substance that could enter the potable system is toxic, poisonous, or microbiologically dangerous. Examples include chemical injection systems, sewage, boiler water with additives, and irrigation systems supplied by a non-potable source. A high-hazard cross-connection requires a high-protection assembly.
- Non-health hazard (low hazard): The substance is objectionable or aesthetically unpleasant but not a danger to health—for example, a connection to a clean water heating system without additives. A lower-protection assembly may be acceptable, depending on the authority having jurisdiction (AHJ).
Always confirm the hazard classification with your local water authority before specifying an assembly. ASSE standards and your state plumbing code both govern this determination.
The Four Major Assembly Types
Atmospheric Vacuum Breaker (AVB): Protects against back-siphonage only—it cannot protect against backpressure. It must be installed at least six inches above the highest downstream outlet and must never be under continuous pressure for more than twelve hours. The AVB is not field-testable in the same way as other assemblies and is used for low-hazard, intermittent-use applications such as hose bibbs.
Pressure Vacuum Breaker (PVB): Protects against back-siphonage only. It can remain under continuous pressure, which makes it suitable for irrigation systems. It must be installed at least twelve inches above the highest downstream outlet. The PVB contains a loaded check valve and an air inlet valve; it is field-testable.
Double Check Valve Assembly (DCVA): Protects against both back-siphonage and backpressure. Used for low-hazard applications such as fire sprinkler systems supplied by potable water and commercial dishwasher supply lines. It contains two independently acting check valves and four test cocks. It may be installed in a pit or horizontally.
Reduced-Pressure Zone Assembly (RPZ or RPZA): The highest level of protection. Used for high-hazard cross-connections. Contains two independently acting check valves separated by a reduced-pressure zone, plus a differential pressure relief valve that opens to atmosphere if the zone pressure rises above a safe differential. The relief valve discharge must drain freely; never plug it. The RPZ is appropriate for boiler-feed connections with chemical additives, reclaimed-water cross-connections, and medical or industrial facilities.
Field Testing Safety
Before any field test:
- Follow lockout/tagout (LOTO) procedures when isolating the assembly; verify zero energy before attaching or removing test equipment.
- Wear appropriate PPE: safety glasses at minimum; chemical-resistant gloves if testing near process fluids; hearing protection in loud mechanical rooms.
- Know the location of the nearest drain; the RPZ relief valve may discharge a significant volume of water during testing.
- Confirm the test kit (differential pressure gauge kit) is calibrated and within its calibration interval before use.
Field Test Procedure Overview: RPZ Assembly
The ASSE-recognized field test sequence for an RPZ uses a differential pressure gauge kit with test hoses attached to the test cocks. The critical measured value is the differential across each check valve and the pressure relief valve opening point. In brief:
1. Notify the downstream user that flow will be interrupted.
2. Attach test kit hoses to test cocks 2 and 3 (middle test cocks) with shutoff valve No. 2 closed.
3. Slowly open test cocks; bleed air from hoses; read and record differential across Check No. 1.
4. Reposition hoses to test Check No. 2 differential.
5. Test the relief valve opening differential by slowly reducing upstream pressure until the relief valve opens; record the opening differential.
6. Compare all readings to the manufacturer's minimum passing criteria and local authority requirements.
7. Complete the standard field test report form with date, location, assembly make/model/serial number, test results, and pass/fail determination.
The DCVA field test follows a similar sequence but evaluates two check valves without a relief valve; the pass/fail threshold is a minimum pressure differential held across each check.
Reporting and Certification
A completed field test report must be submitted to the local water authority or AHJ within the timeframe they require. The report documents your certification number, the assembly tested, conditions found, and whether the assembly passed or required repair. Falsifying a field test report is a violation of your certification and may carry legal consequences.
For the ASSE backflow tester certification exam, expect questions drawn from: cross-connection identification, hazard classification, assembly selection, installation requirements, test procedures and pass/fail criteria, and report completion. Know each assembly's limitations (backpressure vs. back-siphonage protection) and the conditions under which each may be installed.
Key terms9
Cross-connectionAny physical link between a potable water supply and a source of contamination or pollution, actual or potential.
Back-siphonageBackflow caused by negative (sub-atmospheric) pressure in the supply piping, which draws downstream fluid back into the potable system.
BackpressureBackflow caused when downstream pressure exceeds supply pressure, forcing fluid back toward the potable supply.
Health hazard (high hazard)A cross-connection in which the contaminant on the downstream side is toxic, poisonous, or microbiologically dangerous to human health.
Reduced-Pressure Zone Assembly (RPZ)A backflow prevention assembly containing two check valves and a differential pressure relief valve that vents to atmosphere; provides the highest level of protection and is used for high-hazard cross-connections.
Double Check Valve Assembly (DCVA)A backflow prevention assembly with two independently acting check valves; protects against both back-siphonage and backpressure for low-hazard applications.
Pressure Vacuum Breaker (PVB)A back-siphonage-only assembly that can remain under continuous pressure; commonly used for irrigation systems and installed at least 12 inches above the highest downstream outlet.
Differential pressure gauge test kitThe calibrated instrument used by a certified backflow tester to measure pressure differentials across check valves and relief valves during field testing.
Authority Having Jurisdiction (AHJ)The governmental body—typically the local water authority or building department—responsible for enforcing plumbing codes and backflow prevention requirements in a given area.
Worked examples3
1. During an RPZ field test, Check Valve No. 1 holds a differential of 8.0 psid and Check Valve No. 2 holds a differential of 4.5 psid. The relief valve opens at a differential of 3.2 psid. The manufacturer's minimum passing differentials are: Check No. 1 ≥ 5.0 psid, Check No. 2 ≥ 1.0 psid, relief valve opening ≥ 2.0 psid. Does the assembly pass or fail, and why?
- Compare Check No. 1 reading to minimum: 8.0 psid ≥ 5.0 psid — PASS.
- Compare Check No. 2 reading to minimum: 4.5 psid ≥ 1.0 psid — PASS.
- Compare relief valve opening differential to minimum: 3.2 psid ≥ 2.0 psid — PASS.
- All three criteria are met; record results on the field test report form and mark the assembly as PASS.
Answer: The assembly passes all three test criteria. Record 8.0 psid / 4.5 psid / 3.2 psid on the report and indicate PASS.
2. During a DCVA field test, Check Valve No. 1 holds a differential of 0.8 psid and Check Valve No. 2 holds a differential of 2.1 psid. The minimum passing differential for each check valve is 1.0 psid. Does the assembly pass or fail?
- Compare Check No. 1 reading to minimum: 0.8 psid < 1.0 psid — FAIL.
- Compare Check No. 2 reading to minimum: 2.1 psid ≥ 1.0 psid — PASS.
- Because Check No. 1 fails to hold the minimum differential, the overall assembly result is FAIL.
- Document the failed check valve on the field test report, notify the owner, and report to the AHJ as required.
Answer: The DCVA fails. Check Valve No. 1 holds only 0.8 psid, which is below the 1.0 psid minimum. The assembly must be repaired and retested.
3. A building has a chemical-injection system connected to the potable supply. The downstream fluid contains a toxic inhibitor. The supply pressure is 65 psi and the downstream system can develop up to 80 psi. Which assembly type is required, and why?
- Identify the hazard level: the downstream fluid contains a toxic chemical — this is a high-hazard (health hazard) cross-connection.
- Identify the backflow condition: downstream pressure (80 psi) can exceed supply pressure (65 psi), creating a backpressure condition in addition to back-siphonage risk.
- An AVB or PVB cannot be used because neither protects against backpressure.
- A DCVA cannot be used because the hazard is classified as a health hazard, which requires a higher-protection assembly.
- The RPZ assembly protects against both backpressure and back-siphonage and is rated for high-hazard installations — it is the required assembly.
Answer: A Reduced-Pressure Zone (RPZ) assembly is required because the cross-connection is a high health hazard and the downstream system can generate backpressure exceeding supply pressure.
In class: Instructor reviews the ASSE certification content framework—cross-connection control principles, degree-of-hazard classification (health hazard vs. non-health hazard), assembly types (pressure vacuum breaker, reduced-pressure zone assembly, double check valve assembly, atmospheric vacuum breaker), applicable standards referenced by ASSE, installation requirements, and the field test procedure for each assembly type—using diagrams and actual assemblies on the demonstration bench; students annotate their course 8 (Backflow) notes with exam-relevant details. · Instructor performs a live demonstration of the standard field test procedure on an RPZ assembly and a double-check valve assembly using a differential pressure gauge test kit, narrating each step and the pass/fail criteria; students then perform the same procedures in pairs under direct supervision, with each student completing at least one full test sequence and documenting results on a standard field test report form. · Students complete a 30-question ASSE-style practice exam covering cross-connection identification, assembly selection, test procedures, and reporting requirements; they grade their papers and compare results with their tracking sheet to confirm readiness or flag remaining gaps.
Materials: RPZ assembly, double check valve assembly, pressure vacuum breaker assembly (bench-mounted), differential pressure gauge test kit, ASSE field test report forms, ASSE published study materials and referenced standards documents, instructor-prepared practice question bank, personal score-tracking sheet
Check: Students correctly perform a complete field test sequence on at least one assembly type with no procedural errors (instructor observes using a step-by-step checklist; all critical steps must be performed in correct order with correct pass/fail determination) AND score 70% or higher on the 30-question ASSE-style practice written exam.
Practice check8