newSchoolWorks.com › VoTechWorks › Building & Construction › Plumbing & Pipefitting › Gas Piping Systems for Plumbers › Lesson 5
BLD-PLUM06-06 · Lesson 5 · 14 clock hours · theory

Gas Pipe Sizing Using Code Tables

Objective. The student will calculate the pipe size for each segment of a residential gas distribution system using the IFGC longest-length method and appliance BTU ratings.

Why Pipe Sizing Matters

Under-sized gas pipe starves appliances of fuel, causing incomplete combustion, pilot outages, and dangerous carbon monoxide production. Over-sized pipe wastes money and can create low-velocity conditions that allow condensate and debris to accumulate. Every segment of a residential gas distribution system must be sized to deliver the required flow at adequate pressure. The International Fuel Gas Code (IFGC) provides prescriptive sizing tables that make this process straightforward when you follow a systematic method.

Understanding Gas Demand

Natural gas appliances are rated in British Thermal Units per hour (BTU/h) of input — not output. The input rating is the fuel consumed, and it appears on the appliance nameplate and in the manufacturer's data sheet. To use IFGC pipe-sizing tables, you must convert BTU/h to cubic feet per hour (CFH) of natural gas.

Natural gas has a heating value of approximately 1,000 BTU per cubic foot at standard conditions. Use this factor for all residential natural-gas sizing unless your jurisdiction or the gas utility specifies a different heating value.

Conversion formula:

> CFH = BTU/h ÷ 1,000

For example, a furnace rated at 80,000 BTU/h requires 80 CFH. A water heater rated at 40,000 BTU/h requires 40 CFH.

The Longest-Length Method — Step by Step

The IFGC longest-length method (sometimes called the single longest-length method) uses one conservative pipe length — the longest run from the meter or service regulator to any appliance — to size all segments in the system. This approach is intentionally conservative and slightly over-sizes upstream segments, but it is fast, permitted by code for typical residential systems, and eliminates the need for pressure-drop calculations on each segment.

Step 1 — Determine the longest length.

Trace every possible path from the meter outlet to each appliance. Measure or scale the total pipe length along each path. The longest of those measured distances is your longest length. Use this single value for every segment in the system.

Step 2 — Convert all appliance ratings to CFH.

List every appliance and convert its BTU/h input rating to CFH using the formula above.

Step 3 — Calculate the demand for each segment.

Work from the meter toward each appliance. Each segment carries the combined demand of all appliances it feeds. The segment nearest the meter carries the total system demand. At each tee, the flow splits: each branch carries only the appliances downstream of that branch point.

Step 4 — Enter the IFGC sizing table.

Select the table that matches your pipe material (Schedule 40 steel, CSST, etc.) and the system pressure (typically 0.5 psi or less for residential low-pressure systems). Find the row for your longest length, then read across to find the column whose CFH capacity equals or exceeds your segment demand. The column header is your minimum pipe size. Never round down.

Step 5 — Record and check.

Record the pipe size for every segment and confirm that the table capacity at that size meets or exceeds the demand for that segment. Show your work — inspectors and instructors both require it.

Reading the IFGC Tables Correctly

The tables are organized by pipe material and pressure. Rows represent pipe lengths in feet; columns represent nominal pipe sizes. The table value is the maximum allowable CFH for that length and size. If your demand falls between two row values, always use the longer length row (conservative). If your CFH demand falls between two column capacities, always choose the larger pipe size (conservative).

For systems with CSST (corrugated stainless-steel tubing), use the CSST-specific table because CSST has different flow characteristics than steel pipe. Never mix the two tables for the same segment.

Meter and Total Demand

The gas utility and the meter must also be capable of supplying the total connected load. Sum the CFH for every appliance in the building. This total is the demand at the meter. In practice, not all appliances run simultaneously, but the IFGC longest-length method assumes simultaneous operation — a conservative and code-compliant assumption.

Safety Points

Practical Tip

Draw a simple isometric or single-line sketch of every system you size. Label each segment with its length and the appliances it feeds. This makes it easy to identify the longest path, calculate segment demands, and catch errors before you enter the table.

Key terms8

Input ratingThe rate at which an appliance consumes fuel, expressed in BTU/h and shown on the nameplate; always use input rating — not output — for pipe sizing.
CFH (cubic feet per hour)The unit of gas flow used in IFGC sizing tables; calculated by dividing the appliance BTU/h input rating by the heating value of the gas (approximately 1,000 BTU/cf for natural gas).
Longest-length methodAn IFGC-permitted pipe-sizing procedure in which the single longest pipe run from the meter to any appliance is used as the design length for every segment in the system.
Segment demandThe total CFH that a specific pipe segment must carry, equal to the sum of the CFH demands of all appliances fed by that segment.
Total connected loadThe sum of the CFH demands of all appliances served by the meter; used to verify meter and service capacity.
IFGCInternational Fuel Gas Code; the model code that governs the design, installation, and inspection of fuel-gas piping systems in most US jurisdictions.
CSST (corrugated stainless-steel tubing)A flexible gas-piping product with its own IFGC sizing table; must not be sized using steel-pipe tables, and must be bonded per manufacturer listing requirements.
Pressure dropThe reduction in gas pressure as gas flows through pipe due to friction; the longest-length method accounts for pressure drop conservatively without requiring individual segment calculations.

Worked examples4

1. Convert three appliance input ratings to CFH: water heater 40,000 BTU/h; furnace 100,000 BTU/h; gas dryer 22,000 BTU/h.
  1. Use the formula: CFH = BTU/h ÷ 1,000
  2. Water heater: 40,000 ÷ 1,000 = 40 CFH
  3. Furnace: 100,000 ÷ 1,000 = 100 CFH
  4. Gas dryer: 22,000 ÷ 1,000 = 22 CFH
  5. Total connected load = 40 + 100 + 22 = 162 CFH
Answer: Water heater: 40 CFH; Furnace: 100 CFH; Dryer: 22 CFH; Total: 162 CFH
2. A two-appliance system has a furnace (80,000 BTU/h) and a water heater (40,000 BTU/h). The meter is at one end. Segment A runs 30 ft from the meter to a tee. From the tee, Segment B runs 20 ft to the furnace and Segment C runs 15 ft to the water heater. Identify the longest length and the demand for each segment.
  1. Convert to CFH: Furnace = 80,000 ÷ 1,000 = 80 CFH; Water heater = 40,000 ÷ 1,000 = 40 CFH
  2. Find each path length from meter to appliance: Path to furnace = Segment A + Segment B = 30 + 20 = 50 ft; Path to water heater = Segment A + Segment C = 30 + 15 = 45 ft
  3. Longest length = 50 ft (path to furnace). Use 50 ft for all segments.
  4. Segment A feeds both appliances: demand = 80 + 40 = 120 CFH
  5. Segment B feeds only the furnace: demand = 80 CFH
  6. Segment C feeds only the water heater: demand = 40 CFH
Answer: Longest length = 50 ft; Segment A demand = 120 CFH; Segment B demand = 80 CFH; Segment C demand = 40 CFH
3. Using the demands from the previous example (longest length 50 ft; Segment A 120 CFH; Segment B 80 CFH; Segment C 40 CFH), determine the minimum Schedule 40 steel pipe size for each segment. Use the following excerpt from a sample IFGC low-pressure natural gas table for Schedule 40 steel pipe at 50 ft: 1/2 in = 32 CFH; 3/4 in = 72 CFH; 1 in = 143 CFH; 1-1/4 in = 278 CFH.
  1. Segment A requires 120 CFH. At 50 ft: 3/4 in gives 72 CFH (not enough); 1 in gives 143 CFH (sufficient). Select 1 in.
  2. Segment B requires 80 CFH. At 50 ft: 3/4 in gives 72 CFH (not enough); 1 in gives 143 CFH (sufficient). Select 1 in.
  3. Segment C requires 40 CFH. At 50 ft: 1/2 in gives 32 CFH (not enough); 3/4 in gives 72 CFH (sufficient). Select 3/4 in.
  4. Always round up to the next larger size when demand exceeds the table value — never round down.
Answer: Segment A: 1 in; Segment B: 1 in; Segment C: 3/4 in
4. A four-appliance residential system has the following appliances: Range 65,000 BTU/h; Furnace 100,000 BTU/h; Water heater 40,000 BTU/h; Dryer 22,000 BTU/h. The longest path from the meter to any appliance is 60 ft. What is the total meter demand in CFH, and what is the demand on the main segment leaving the meter?
  1. Convert all appliances: Range = 65,000 ÷ 1,000 = 65 CFH; Furnace = 100,000 ÷ 1,000 = 100 CFH; Water heater = 40,000 ÷ 1,000 = 40 CFH; Dryer = 22,000 ÷ 1,000 = 22 CFH
  2. Total meter demand = 65 + 100 + 40 + 22 = 227 CFH
  3. The main segment leaving the meter feeds all four appliances, so its demand equals the total connected load: 227 CFH
  4. You would then enter the IFGC Schedule 40 steel pipe table at the 60 ft row and find the column whose capacity equals or exceeds 227 CFH to size that main segment.
Answer: Total meter demand = 227 CFH; Main segment demand = 227 CFH

The math in this lesson2

Learners convert appliance BTU/h ratings to CFH of natural gas at about 1,000 BTU per cubic foot.
N-Q.1F-IF.4
Brush up in the math halls at newSchoolWorks.com:
In class: Instructor demonstrates the longest-length sizing method step by step on a two-appliance example, showing how to convert appliance input ratings to cubic feet per hour and apply IFGC sizing tables for steel pipe. · Students complete a structured worksheet sizing a three-appliance system (water heater, furnace, dryer) with instructor-provided BTU inputs and pipe lengths, checking their segment sizes against the answer key in pairs. · Each student independently sizes a four-appliance residential system from a provided load schedule and isometric; answers are submitted and checked against instructor key before the next lesson.
Materials: IFGC sizing tables (steel pipe and CSST), appliance BTU data sheets, sizing worksheet packet, calculators, NCCER Plumbing Level 3 module
Check: Independent sizing problem graded by instructor; all pipe segments must be correctly sized with work shown. Passing: no more than one segment error and correct final meter demand. Students with more than one error complete a remedial problem before advancing.

Practice check8

Answer each question, then check it. Nothing is recorded; this is your own practice.

NCCER Plumbing L3 — Gas Piping
1. What heating value (BTU per cubic foot) is used to convert natural gas appliance BTU/h ratings to CFH for IFGC pipe sizing?
NCCER Plumbing L3 — Gas Piping
2. A gas dryer has an input rating of 22,000 BTU/h. What is its demand in cubic feet per hour (CFH)?
NCCER Plumbing L3 — Gas Piping
3. In the IFGC longest-length method, which pipe length is used to size every segment in the system?
NCCER Plumbing L3 — Gas Piping
4. A segment of gas pipe feeds both a furnace (100 CFH) and a water heater (40 CFH). What demand must that segment be sized to carry?
NCCER Plumbing L3 — Gas Piping
5. When a segment's CFH demand falls between two capacity values in the IFGC sizing table, what must you do?
NCCER Plumbing L3 — Gas Piping
6. A technician wants to size CSST for a branch feeding a range. Which IFGC sizing table should be used?
State Journeyman Plumber — Code Compliance
7. Before performing a pressure test on a newly installed gas piping system, a plumber should verify the leak-test procedure by referencing:
NCCER Plumbing L3 — Gas Piping
8. A residential system serves a furnace (100,000 BTU/h), a water heater (40,000 BTU/h), a range (60,000 BTU/h), and a dryer (22,000 BTU/h). What is the total meter demand in CFH?
Record this lesson on my transcript. Sign in with your key and enrollment email to record lessons (enroll free if you have no key). This page stays open to read and practise.