Objective. The student will identify IFGC-approved pipe materials, fittings, and manual shutoff valves for gas service and describe prohibited materials and why they are banned.
Selecting the right material for a gas piping system is not a preference—it is a code requirement. The International Fuel Gas Code (IFGC) specifies which materials are approved for gas service and which are prohibited. Using a prohibited material can result in a failed inspection, required removal of work, and serious safety hazards including gas leaks and explosions. Every plumber must be able to identify approved materials on sight and explain why banned materials are banned.
---
Black steel pipe is the most common material for interior gas distribution. It is strong, widely available, and compatible with natural gas and propane. Fittings are malleable iron (threaded) or steel (welded). Joints are made with approved pipe-joint compound or tape listed for gas service. Standard steel pipe uses NPT (National Pipe Taper) threads; all joints must be leak-tested after assembly.
Corrugated Stainless Steel Tubing (CSST) is a flexible piping system used to route gas from a rigid distribution point to appliances. CSST is faster to install than rigid pipe and can be routed around obstacles. It must be installed strictly per the manufacturer's listing and installation guide—fittings, bend radii, bonding, and grounding requirements are all manufacturer-specific and code-enforceable. Because CSST can be damaged by lightning-induced electrical arcing, bonding is required by code; some jurisdictions have additional local requirements. Never mix CSST fittings from different manufacturers.
Copper and copper-alloy tubing is approved in some jurisdictions for gas service only when the gas does not contain more than a trace of hydrogen sulfide, which would corrode copper. Copper used for gas is ACR (Air Conditioning and Refrigeration) tube, which is cleaned and capped at the factory. Standard plumbing copper is not the same product. Check your local jurisdiction: some states prohibit copper for gas entirely. Fittings are flared or brazed—no solder joints are permitted in gas service.
Polyethylene (PE) gas pipe is approved for underground exterior use only. It is never permitted above grade or inside buildings. PE pipe is joined by heat fusion or approved mechanical fittings and must be installed with a tracer wire for locating. It is yellow or marked yellow for identification.
---
Galvanized steel pipe is prohibited for gas interior piping. The zinc coating on the interior of galvanized pipe can flake off over time when exposed to gas, and those flakes travel downstream and clog appliance controls, orifices, and pressure regulators. The IFGC prohibits it for gas because of this fouling hazard, not because the pipe itself leaks immediately.
Cast iron pipe is prohibited for gas service. Cast iron is brittle and cannot tolerate the vibration and minor movement that a gas system encounters. A crack in a cast iron gas joint is a serious hazard.
Standard PVC or CPVC plastic pipe is prohibited for gas service inside buildings. These plastics are not listed for fuel gas and can be damaged by solvents present in some gas streams; they also lack the mechanical strength required.
Unlined or non-listed flexible connectors and aluminum pipe are likewise not approved for gas distribution piping.
---
For black steel systems, malleable iron fittings (elbows, tees, couplings, unions) are standard. Gray cast iron fittings are not interchangeable—they are brittle and not approved for gas. Street elbows and bushings are permitted where needed. A union must be installed wherever a section of pipe must be removable for service. All threaded joints require pipe-joint compound or PTFE tape listed for gas service—standard white plumbing tape is not rated for gas and must not be used.
---
The IFGC requires a manual shutoff valve upstream of every appliance. Three types appear in gas work:
Valves must be listed for gas service and accessible without tools or removing permanent construction. Never use a gate valve as a gas shutoff—gate valves are not reliable for this application and are not listed for gas isolation.
---