Objective. Students will distinguish accepted residential wiring methods (NM cable, armored cable, conduit), identify wiring-age indicators, and use a receptacle tester and non-contact voltage tester to evaluate outlets and switches within the inspector's approved scope.
This lesson, its worked examples and its practice questions has not yet been verified by a credentialed professional in the field or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.
VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.
As a home inspector, you are not an electrician, but you must recognize the wiring methods present in a home, identify age-related and safety concerns, and test devices within your approved scope. This lesson covers the major residential wiring types, how to read a receptacle tester, and how to document what you find.
NM-B Cable (Non-Metallic Sheathed Cable / Romex) is the most common wiring method in residential construction today. It consists of insulated conductors and a bare ground wire wrapped in a plastic jacket. The "B" designation indicates 90°C-rated insulation on the conductors. NM cable must be protected from physical damage and is not permitted in wet or corrosive locations, or where embedded in concrete. In living areas it must be run through studs or protected if exposed.
Armored Cable (AC/BX) uses a flexible metal spiral jacket and has been used in homes since the early twentieth century. Older BX cable contains no separate ground wire — the metal jacket serves as the equipment ground, which can be unreliable if connectors are loose. Modern AC cable includes a bonding strip. Inspect connectors and conduit fittings carefully; a loose fitting degrades the ground path.
Conduit with THHN Conductors is common in garages, exposed basement runs, and service entries. Conduit types include EMT (electrical metallic tubing), PVC, and flexible conduit. THHN is a single thermoplastic insulated conductor pulled into conduit. This system is more durable than NM cable in exposed locations.
Knob-and-Tube (K&T) Wiring was standard from roughly the 1880s through the 1940s. It uses individual conductors run through ceramic knobs (support) and ceramic tubes (where passing through framing). K&T has no equipment ground and the insulation is fabric or rubber that becomes brittle with age. Many insurers refuse to cover homes with active K&T. Key concerns: insulation condition, improper splices outside junction boxes, and covering with insulation (which traps heat).
Aluminum Branch-Circuit Wiring was used extensively in residential construction from the mid-1960s through the mid-1970s as copper prices rose. Aluminum expands and contracts more than copper, causing connections to loosen over time and creating overheating and fire risk at devices. Look for the marking "AL" or "ALUMINUM" on the cable jacket. Devices must be rated CO/ALR or connections must be made with approved methods. Report aluminum wiring as a significant finding requiring evaluation by a licensed electrician.
Service Entrance (SE) Cable brings power from the utility connection into the panel. It is not a branch-circuit wiring method but you will see it in every inspection. Note its condition at the weatherhead, drip loop, and entry point.
The wiring method itself tells you roughly when the home was built or last rewired. K&T suggests pre-1950 construction. Two-wire NM without a ground conductor (two slots only at outlets) is typical of homes wired before grounding was commonly required. Aluminum branch wiring points to mid-1960s to mid-1970s. Modern NM-B with a ground is typical of construction from the 1980s forward. Document the wiring era in your report; it helps clients understand what further evaluation may be needed.
Non-Contact Voltage Tester (NCVT): Before touching any device, terminal, or wire, use your NCVT to confirm whether voltage is present. Hold the tip near the outlet slot, wire, or cable. A beep or light indicates live voltage. Always verify the tester is working before and after use on a known live source. The NCVT is your first line of defense — it keeps your hands away from energized parts.
Receptacle Tester (Three-Light): Plug the tester into an outlet and read the three indicator lights against the legend on the tester body. The standard conditions you will encounter are:
GFCI receptacles must be tested with the TEST and RESET buttons, not with the receptacle tester alone, because some GFCI devices will indicate correct wiring on a basic tester even when the GFCI function is not working.
PPE Requirements: Wear safety glasses during all lab work. When working at or near energized equipment, wear insulated gloves rated at minimum Class 00. Follow the lab's lockout/tagout procedure for the mock room — confirm power is off before handling any open wiring, and confirm power is on only at the supervised practice station.
Double-tapped circuit breaker: Two conductors connected to a single breaker terminal that is rated for only one conductor. This is a defect unless the breaker is listed and labeled for two conductors.
Exposed NM cable in a living area: NM cable must be protected from physical damage. Cable run across a basement ceiling that is a finished living area, or across a wall surface without protection, is a defect.
Missing cover plate: Every junction box, switch box, and outlet box must have a cover plate. An open box is a shock and fire hazard.
Missing GFCI protection: Ground fault circuit interrupter protection is required in kitchens, bathrooms, garages, outdoors, crawl spaces, unfinished basements, and near pools and hot tubs. The specific locations have expanded over successive code editions; inspect and report based on the standards adopted by your jurisdiction.
Improper splicing outside a box: Wire splices must be made inside an accessible, covered junction box. Splices made inside a wall cavity or under insulation are defects.
A professional report entry names the defect, states its location, explains why it is a concern, and recommends action. Example: "A double-tapped circuit breaker was observed at the main panel on a 20-amp breaker. Double-tapping can cause overheating and nuisance tripping. Recommend evaluation and correction by a licensed electrician." Be specific, be factual, and avoid diagnosing causes beyond your scope.
Answer each question, then check it. Nothing is recorded; this is your own practice.