MFG-INDU16-06 · Lesson 2 · 15 clock hours · demo
PLC Hardware: Power Supplies, CPUs, and Rack Wiring
Objective. Students install a CPU and I/O modules into a PLC rack and connect AC power and chassis ground following NEC wire-sizing and termination practices.
⚠ Pending professional review
This lesson, its worked examples and its practice questions has not yet been verified by a licensed engineer or certified journey-level tradesperson or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.
VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.
PLC Hardware: Power Supplies, CPUs, and Rack Wiring
What a PLC Rack Is and Why It Matters
A programmable logic controller (PLC) system is built on a rack — a metal chassis that holds the CPU, power supply module, and input/output (I/O) modules in a fixed, organized row. The rack provides the mechanical support, the internal backplane bus for data and power, and the grounding path that keeps every module at the same electrical reference. Getting the rack built correctly before any programming begins is not optional: a loose module, an ungrounded chassis, or an undersized wire can damage equipment, corrupt data, or create a shock or arc-flash hazard.
Power Supply Module
The power supply module converts the incoming AC line voltage (typically 120 VAC in US installations) into the regulated DC voltages the rack backplane needs — commonly 5 VDC for logic circuits and sometimes 24 VDC for field devices. A separate 24 VDC power supply is often mounted on the same panel to power sensors and output loads; this supply is external to the rack but must share a common ground reference with it.
Before energizing anything:
- Confirm the supply's input voltage rating matches the panel's line voltage.
- Verify the supply's output current rating is sufficient for all modules and field devices it will feed.
- The power LED on the supply and on the CPU should illuminate solid green when power is healthy. A flashing or red LED signals a fault you must resolve before proceeding.
CPU Module
The central processing unit (CPU) module executes the ladder-logic or other program, manages the I/O scan cycle, and communicates with programming devices. CPUs slide into a dedicated slot — almost always the slot immediately adjacent to the power supply — and connect to the backplane through a keyed edge connector. Key points:
- Seat firmly: Push the module straight in until the connector is fully engaged, then secure the retaining screw or latch per the hardware manual.
- Handle with care: CPUs contain non-volatile memory and CMOS circuitry sensitive to electrostatic discharge (ESD). Touch a grounded surface or wear an ESD wrist strap before handling.
- Mode switch: Most CPUs have a RUN/PROG/REMOTE switch. Set it to PROG (program mode) before any download and before initial power-up in a lab setting.
I/O Modules
Input modules sense field signals (pushbuttons, limit switches, sensors). Output modules energize field devices (contactors, solenoid valves, indicator lights). Both types plug into numbered I/O slots on the backplane. The slot number determines the module's address in the program, so installing a module in the wrong slot will cause the wrong program tags to activate — a safety risk in production.
Always check the hardware manual for the maximum number of I/O modules a rack supports and whether any slots are reserved.
DIN-Rail Mounting
The external 24 VDC supply and terminal blocks are typically mounted on DIN rail — a standardized steel channel (35 mm wide is most common) fastened to the panel backplate. To mount a device:
1. Tilt the device so its upper DIN-rail clip hooks onto the rail.
2. Press down and inward until the spring-loaded lower clip snaps onto the rail.
3. Slide the device to its final position and secure with end stops.
DIN rail must be fastened to a grounded metal enclosure so the rail itself becomes part of the equipment ground path.
Wiring: NEC Guidance and Wire Sizing
Industrial control panel wiring in the US falls under NEC Article 409 (Industrial Control Panels) and for industrial machinery under Article 670. These articles govern wire sizing, insulation ratings, overcurrent protection, and marking. Key practices for this lab:
- Use copper conductors rated for the temperature of the environment (75 °C minimum is standard for most industrial panels).
- Size wires to carry the continuous current without exceeding the conductor's ampacity from NEC Table 310.16 (or the equivalent column for the installation method).
- Use stranded wire inside enclosures for flexibility; solid wire is prone to breaking at terminal screws from repeated vibration.
- Strip insulation only as far as the terminal requires — bare copper should not be visible beyond the terminal body.
- Torque terminal screws to the value listed in the hardware manual or on the terminal block label. Under-torqued connections create resistance, heat, and arc hazards; over-torqued connections crack the terminal body or nick conductors. A calibrated torque screwdriver is the right tool.
Equipment Grounding
The chassis ground wire connects the rack's grounding lug to the panel's equipment grounding conductor (EGC), which in turn connects to the building grounding system. This path clears ground faults rapidly, tripping the overcurrent device and removing the shock hazard. The ground wire must be:
- Green insulation or green with a yellow stripe (NEC color code for EGC).
- Sized at least as large as the largest ungrounded conductor supplying the panel, per NEC requirements.
- Terminated with a ring or fork lug, not wrapped bare around a screw.
Safety Before, During, and After
Lockout/Tagout (LOTO): The training rack is de-energized before class. Before reconnecting power, confirm with the instructor. Never bypass LOTO.
PPE: Safety glasses are required when working near energized panels or when inserting modules (debris can fall). When the panel is confirmed energized, arc-flash boundaries apply — follow site PPE requirements.
Multimeter check: Before applying power, use your multimeter set to resistance (Ω) to verify there is no short between the 24 VDC positive rail and the chassis ground rail. A short now prevents equipment damage later.
Wire Marking and Documentation
Every wire in an industrial panel must be labeled at both ends with a unique wire number. Wire-marking tags (heat-shrink or clip-on) prevent troubleshooting errors. Your point-to-point wiring diagram documents the source terminal, destination terminal, wire number, wire gauge, and color for every conductor. This diagram becomes the maintenance record for the panel's lifetime.
Key terms10
BackplaneThe internal bus board at the rear of a PLC rack that carries power and data signals between the power supply, CPU, and I/O modules through their edge connectors.
CPU moduleThe central processing unit card in a PLC rack; it executes the control program, manages the I/O scan cycle, and communicates with programming devices.
DIN railA standardized metal channel (most commonly 35 mm wide) mounted inside an enclosure to provide a mechanical attachment point for power supplies, terminal blocks, and other panel components.
Equipment grounding conductor (EGC)The green or green-with-yellow-stripe wire that bonds metal enclosures and equipment frames to the building ground system, providing a low-impedance fault-current path to trip overcurrent protection.
I/O moduleA plug-in card that interfaces the PLC backplane with field devices; input modules read sensor signals and output modules energize actuators.
Torque screwdriverA calibrated hand tool that applies a set maximum torque to a fastener, preventing under- or over-tightening of terminal screws.
NEC Article 409The section of the National Electrical Code that governs the construction, installation, and marking requirements for industrial control panels.
Point-to-point wiring diagramA document that lists every wire in a panel by wire number and shows both the source terminal and the destination terminal, used for installation verification and maintenance.
Electrostatic discharge (ESD)A sudden transfer of static electricity between objects at different potentials; can permanently damage CMOS circuitry inside CPU and I/O modules.
Power-OK LEDAn indicator light on a PLC power supply or CPU module that illuminates solid when regulated output voltages are within specification, confirming the rack is ready for programming.
Worked examples4
1. The 24 VDC external power supply is rated 5 A output. You need to verify the total current draw of the field devices connected to it does not exceed that rating. Three sensors each draw 80 mA and two solenoid valves each draw 350 mA. What is the total current draw, and is the supply adequate?
- Convert all values to the same unit (mA): sensors = 3 × 80 mA = 240 mA; solenoids = 2 × 350 mA = 700 mA.
- Add the loads: 240 mA + 700 mA = 940 mA total.
- Convert to amps: 940 mA ÷ 1000 = 0.94 A.
- Compare to supply rating: 0.94 A < 5 A, so the supply has ample capacity.
Answer: Total draw is 0.94 A. The 5 A supply is adequate, with 4.06 A of headroom.
2. Your hardware manual states terminal screws on the I/O module require 0.5 N·m torque. Your torque screwdriver is graduated in in·lb. What setting should you use? (1 N·m = 8.851 in·lb)
- Multiply the required torque in N·m by the conversion factor: 0.5 N·m × 8.851 in·lb/N·m.
- 0.5 × 8.851 = 4.4255 in·lb.
- Round to the nearest practical increment on the screwdriver: set to approximately 4.4 in·lb.
Answer: Set the torque screwdriver to approximately 4.4 in·lb.
3. You measure the resistance between the 24 VDC positive bus and chassis ground with your multimeter before applying power. The display shows 0.3 Ω. Should you apply power? What does this reading suggest?
- A healthy, de-energized DC bus separated from chassis ground should show very high resistance (megohms or OL on the meter), because the positive rail and ground rail are electrically isolated except through internal circuitry.
- 0.3 Ω is essentially a short circuit — far too low.
- Do not apply power. Notify the instructor and trace wiring to find the unintended connection before energizing.
Answer: Do not apply power. A reading of 0.3 Ω indicates a near-short between the positive bus and chassis ground; the fault must be located and corrected first.
4. A wire feeding the rack power supply carries a continuous load of 3 A at 120 VAC. Using NEC ampacity principles, must you use 14 AWG or 12 AWG copper THHN if the raceway has three current-carrying conductors and the ambient temperature is within the standard 30 °C range?
- NEC Table 310.16 lists 14 AWG THHN (90 °C column) at 25 A ampacity before derating; however, the equipment is protected by a 15 A overcurrent device maximum for 14 AWG.
- For continuous loads, NEC requires the conductor and overcurrent device be rated at 125% of the continuous load: 3 A × 1.25 = 3.75 A minimum.
- Both 14 AWG and 12 AWG easily exceed 3.75 A; however, NEC 409 and standard industrial practice call for a minimum of 14 AWG for branch-circuit conductors inside panels.
- Either size is electrically adequate for this load, but confirm the overcurrent device rating. In practice, many industrial specifications default to 12 AWG for robustness and ease of future load additions.
Answer: Either 14 AWG or 12 AWG THHN is electrically adequate for a 3 A continuous load; both comfortably exceed the 3.75 A minimum (125% of 3 A). Verify the overcurrent device matches the conductor and follow site or panel specifications — 12 AWG is the common conservative choice.
The math in this lesson1
Learners convert terminal torque from N·m to in·lb and total field-device current against a 5 A supply.
N-Q.1
In class: Instructor demonstrates module seating, DIN-rail mounting, and torque requirements for terminal screws on the training rack while students follow along in the hardware manual. · Students work in pairs to install a CPU module and two I/O modules into an empty rack, connect a 24 VDC power supply, and verify LED power-OK indication before any programming begins. · Students trace and label every wire on the training panel using wire-marking tags, then sketch a point-to-point wiring diagram in their lab notebooks and verify it against the instructor's answer key.
Materials: PLC trainer rack (instructor disassembled before class), 24 VDC power supply, DIN rail, wire markers, torque screwdriver, multimeter, NEC codebook reference (Article 409 / 670 overview), hardware installation manual
Check: Instructor inspects completed rack: all modules seated, screws torqued, ground wire present, power LED lit, and wiring diagram matches physical panel — all four criteria must be met for pass.
Practice check8
Answer each question, then check it. Nothing is recorded; this is your own practice.
Record this lesson on my transcript. Sign in with your key and enrollment email to record lessons (enroll free if you have no key). This page stays open to read and practise.