newSchoolWorks.com › VoTechWorks › Agriculture, Environment & Public Service › Water / Wastewater Operator › Water Chemistry for Operators › Lesson 9
AGR-WATE71-02 · Lesson 9 · 10.5 clock hours · theory

Corrosion, Scale, and Chemical Stabilization

Objective. Students will identify the electrochemical mechanisms of pipe corrosion, explain methods operators use to control corrosion and scale formation, and calculate a basic corrosion-inhibitor dose.

⚠ Pending professional review

This lesson, its worked examples and its practice questions has not yet been verified by a licensed professional in the field or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.

VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.

Corrosion, Scale, and Chemical Stabilization

Corrosion and scale are two opposite problems that operators must balance every day. Corrosion destroys pipe metal, releases contaminants into drinking water, and shortens system life. Scale (hard mineral deposits) clogs pipes, reduces flow, and insulates heat-exchange surfaces. Understanding the chemistry behind each problem lets you choose the right control strategy.

How Corrosion Happens

Corrosion in water systems is an electrochemical process. Two types are most important for operators.

Galvanic corrosion occurs when two different metals are in contact in the presence of water. One metal acts as the anode (it oxidizes and loses metal) and the other acts as the cathode (it is protected). The metal higher on the galvanic series corrodes first. A common example is copper pipe connected directly to galvanized iron pipe: the iron corrodes preferentially. Lead solder next to copper fittings is another classic galvanic pair that can release lead into drinking water.

Concentration-cell corrosion (also called differential-aeration corrosion) occurs on a single metal surface when one area has less dissolved oxygen than another. The oxygen-depleted zone becomes the anode and corrodes. This is common under deposits, biofilm, or at crevices in joints.

Key Water-Quality Factors

Several water-quality parameters drive corrosion rate:

Scale Formation

Scale is the opposite of corrosion: water deposits minerals onto pipe walls. The most common scale is calcium carbonate (CaCO₃). While a thin CaCO₃ film is actually protective and desirable, heavy scale restricts flow, increases pumping costs, and can harbor bacteria. Scale also forms from calcium sulfate, magnesium compounds, and silicates in certain source waters.

Corrosion-Control Strategies

pH and alkalinity adjustment is the most fundamental tool. Raising pH toward 8.0–8.5 (within permit limits) slows the electrochemical reaction and encourages a thin protective film. Operators add sodium hydroxide, soda ash (sodium carbonate), or lime to raise pH. Alkalinity is adjusted with sodium bicarbonate or lime.

Calcium carbonate stabilization targets the Langelier Saturation Index (LSI). The LSI compares actual water chemistry to the theoretical equilibrium where water is neither depositing nor dissolving CaCO₃. An LSI near zero is balanced. Negative LSI means corrosive (scale-dissolving) water; positive LSI means scale-depositing water. Operators adjust pH, calcium, and alkalinity to move the LSI toward a slightly positive value, encouraging a thin protective coating without heavy scale.

Orthophosphate addition is a widely used corrosion inhibitor under the Lead and Copper Rule. Orthophosphate ions react with lead and copper at the pipe wall to form insoluble phosphate minerals (such as lead hydroxyapatite and copper phosphate) that coat the surface and limit metal release into the water. Typical target residuals are in the low mg/L range. The chemical feed rate must be calculated precisely to maintain that target throughout the system.

Blending of aggressive and non-aggressive source waters is another strategy when multiple sources are available.

Safety Note

When handling corrosion-control chemicals — orthophosphoric acid, sodium hydroxide, soda ash, or lime — always wear the PPE required by the Safety Data Sheet (SDS): chemical-splash goggles, face shield, acid- or caustic-resistant gloves, and a chemical-resistant apron. Caustic and acid spills on skin or eyes require immediate flushing with large volumes of water for at least 15 minutes. Before servicing any chemical feed pump, follow lockout/tagout (LOTO) procedures to isolate energy and prevent accidental start-up. Store oxidizing chemicals (such as hypochlorite) separately from acids and phosphates.

Calculating a Chemical Feed Rate

The standard concentration–flow–dose relationship is:

Feed rate (lb/day) = Flow (MGD) × Dose (mg/L) × 8.34 lb/gal

For liquid chemical feeds expressed in volume per time, operators convert using the chemical's percent concentration and specific gravity. Always verify units before calculating and check your answer against the system's established dose range.

Key terms8

Galvanic corrosionElectrochemical corrosion that occurs when two dissimilar metals are electrically connected in water; the less noble metal (anode) corrodes preferentially.
Concentration-cell corrosionCorrosion on a single metal surface caused by differences in dissolved-oxygen concentration; oxygen-depleted areas become anodic and corrode.
Langelier Saturation Index (LSI)A calculated index that indicates whether water will tend to dissolve, deposit, or be in equilibrium with calcium carbonate; negative = corrosive, positive = scale-forming, near zero = balanced.
OrthophosphateA phosphate compound added to drinking water as a corrosion inhibitor; it reacts with pipe metals to form a thin, insoluble protective mineral film that reduces lead and copper release.
AlkalinityThe capacity of water to neutralize acid, primarily from bicarbonate and carbonate ions; adequate alkalinity buffers pH and supports protective calcium carbonate film formation.
Passivation layerA thin oxide or mineral film that forms naturally or is induced on a metal surface, slowing further corrosion by limiting contact between the metal and the water.
ScaleHard mineral deposits, most commonly calcium carbonate, that form on pipe walls and equipment surfaces when water is oversaturated with dissolved minerals.
Chemical feed rateThe quantity of chemical added to the water stream per unit of time, calculated from flow rate, target dose, and chemical concentration to achieve a desired treatment residual.

Worked examples4

1. A water system treats 2.5 MGD. The operator wants to achieve a target orthophosphate residual of 1.0 mg/L. How many pounds of orthophosphate must be fed per day? (Assume the chemical is 100% pure for this calculation.)
  1. Write the formula: Feed rate (lb/day) = Flow (MGD) × Dose (mg/L) × 8.34 lb/gal
  2. Substitute the known values: Feed rate = 2.5 MGD × 1.0 mg/L × 8.34 lb/gal
  3. Multiply: 2.5 × 1.0 = 2.5; then 2.5 × 8.34 = 20.85 lb/day
Answer: 20.85 lb/day of orthophosphate
2. The same 2.5 MGD system uses a liquid orthophosphoric acid solution that is 75% pure (by weight) with a specific gravity of 1.58. How many pounds of the liquid solution must be fed per day to deliver 20.85 lb/day of active orthophosphate?
  1. The dose of pure chemical needed is 20.85 lb/day (from the previous example).
  2. Because the solution is only 75% active ingredient, divide by the decimal fraction: 20.85 ÷ 0.75 = 27.80 lb/day of liquid solution.
  3. If a volume is needed, convert using specific gravity: weight of liquid solution per gallon = 8.34 × 1.58 = 13.18 lb/gal.
  4. Volume per day = 27.80 lb/day ÷ 13.18 lb/gal = 2.11 gal/day of liquid solution.
Answer: 27.80 lb/day (or approximately 2.11 gal/day) of the 75% liquid solution
3. An operator converts that daily volume to an hourly pump setting. The chemical feed pump runs continuously. What is the required pump feed rate in gallons per hour?
  1. Daily volume needed = 2.11 gal/day (from previous example).
  2. Convert to hours: 2.11 gal/day ÷ 24 hr/day = 0.088 gal/hr.
  3. Round to a practical setting: approximately 0.09 gal/hr. Verify this is within the pump's rated range.
Answer: Approximately 0.09 gal/hr (or about 88 mL/hr)
4. A 1.0 MGD system needs to raise its pH using sodium hydroxide (NaOH). Lab results show a required dose of 4.0 mg/L. Calculate the daily NaOH feed in pounds per day.
  1. Write the formula: Feed rate (lb/day) = Flow (MGD) × Dose (mg/L) × 8.34 lb/gal
  2. Substitute values: Feed rate = 1.0 × 4.0 × 8.34
  3. Multiply: 1.0 × 4.0 = 4.0; then 4.0 × 8.34 = 33.36 lb/day
Answer: 33.36 lb/day of NaOH

The math in this lesson2

Learners compute orthophosphate feed rate 2.5 MGD × 1.0 mg/L × 8.34 = 20.85 lb/day.
A-SSE.1N-Q.1
Brush up in the math halls at newSchoolWorks.com:
In class: Lecture: galvanic and concentration-cell corrosion, the role of pH, dissolved oxygen, chlorides, and alkalinity in corrosion; corrosion-control strategies (pH adjustment, orthophosphate addition, calcium carbonate stabilization); students take structured notes. · Pipe-section examination: instructor provides samples or photographs of corroded iron, copper, and galvanized pipe sections; students identify corrosion type, probable cause, and recommended treatment response for each sample, recording findings in their lab log. · Dose-calculation exercise: given a flow rate, a target orthophosphate residual, and a chemical concentration, students calculate the required chemical feed rate using the standard concentration-flow-dose formula.
Materials: Corroded pipe sections or high-resolution photographs, reference tables for corrosion control, calculation worksheet, AWWA Distribution System Requirements for Fire Protection or equivalent operator manual, student notebooks.
Check: Pipe-section identification: at least 4 of 5 samples correctly identified with cause and response (80% pass mark); dose calculation within 5% of correct answer; structured notes reviewed for completeness.

Practice check8

Answer each question, then check it. Nothing is recorded; this is your own practice.

Water Treatment — Corrosion Control
1. Which water-quality condition is MOST likely to increase the rate of galvanic corrosion in a distribution system where copper and iron pipe are joined?
Water Treatment — Corrosion Control
2. An operator calculates a Langelier Saturation Index (LSI) of –0.8 for the distribution system. What does this value indicate?
Water Treatment — Chemical Addition
3. Orthophosphate is added to a drinking water system primarily to:
Water Treatment — Dosage Calculations
4. A water system flows at 3.0 MGD. The target orthophosphate dose is 2.0 mg/L. Using the standard formula, what is the required feed rate in pounds per day?
Water Distribution — Corrosion Mechanisms
5. Concentration-cell corrosion most commonly occurs:
Safety — Lockout/Tagout
6. Before servicing a chemical metering pump that delivers sodium hydroxide solution, an operator's FIRST action should be to:
Water Treatment — Lead and Copper Rule Compliance
7. Which combination of water-quality adjustments would BEST stabilize a corrosive, low-alkalinity water supply to reduce lead release from service lines?
Water Treatment — Dosage Calculations
8. A liquid corrosion inhibitor solution is 50% active ingredient by weight with a specific gravity of 1.40. If a system requires 10.0 lb/day of the active ingredient, how many pounds per day of the liquid solution must be fed?