MFG-MECH15-07 · Lesson 3 · 16 clock hours · lab

Electrical Measurement and Signal Tracing in Control Circuits

Objective. Students will use a digital multimeter and clamp meter to measure voltage, current, resistance, and continuity at specified test points in a 120 VAC control circuit and a 24 VDC I/O circuit, and correctly interpret each reading against specification.

⚠ Pending professional review

This lesson, its worked examples and its practice questions has not yet been verified by a licensed engineer or certified journey-level tradesperson or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.

VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.

Electrical Measurement and Signal Tracing in Control Circuits

Why Accurate Measurement Matters

A mechatronics technician who cannot read a meter accurately is guessing, not troubleshooting. Control circuits in manufacturing and marine automation combine 120 VAC power circuits with 24 VDC I/O circuits, relay coils, limit switches, fuses, and PLC input cards. A single misread can send you chasing the wrong component—or expose you to a shock hazard. This lesson teaches you to select the right meter function, place leads correctly, read the result, and compare it to the specification before declaring a component good or bad.

---

Safety First: Before You Touch Anything

Lockout/tagout (LOTO) — OSHA 29 CFR 1910.147. Resistance and continuity checks must be made with power removed and the circuit locked out. Applying an ohmmeter to an energized circuit will damage the meter and can injure you.

NFPA 70E — Electrical Safety in the Workplace. Before working near energized 120 VAC conductors, identify the shock boundary and arc-flash boundary for the panel. At 120 VAC control-panel voltages, the hazard level is typically low, but you must still verify absence of voltage with your meter before touching terminals. Use CAT III rated meters and leads for industrial control panels—CAT III is the minimum category for measurements on distribution panels and building wiring; your meter face should show the rating.

PPE. Wear safety glasses at all times in the lab. Use insulated gloves rated for the voltage when probing energized 120 VAC points. Never bypass a fuse or jumper a safety device to "test" it.

Verify your meter first. Check meter leads for cracked insulation before every session. Test on a known-good voltage source to confirm the meter is functioning before trusting its readings on the fault board.

---

The Digital Multimeter (DMM) — Function Selection

A digital multimeter measures voltage (AC and DC), resistance, and continuity. Selecting the wrong function can blow the meter's internal fuse or damage the unit.

| Function | Selector Position | Leads | Power in Circuit? |

|---|---|---|---|

| AC Voltage | VAC or V~ | COM + V | Yes |

| DC Voltage | VDC or V— | COM + V | Yes |

| Resistance | Ω | COM + V | No — LOTO first |

| Continuity | ))) or diode | COM + V | No — LOTO first |

| DC Current (in-line) | A or mA | COM + A | Yes — break circuit |

For current measurement on a load conductor without breaking the circuit, use a clamp meter. Open the jaw, clamp it around one conductor only (not both), and read AC or DC current directly.

---

Ohm's Law and Power Review

All measurements trace back to three relationships:

In a 120 VAC control circuit, a relay coil rated at 120 VAC / 0.15 A draws about 18 W. If you measure only 90 VAC across the coil, you know the coil is seeing less than rated voltage—look upstream for a voltage drop across a loose terminal or a failing contact.

In a 24 VDC I/O circuit, a PLC input card presents a known input impedance (often several kilohms). A sensor output should sit at 24 VDC (logic high) or near 0 VDC (logic low). Readings in between usually mean a failing sensor or a wiring fault.

---

Signal Tracing: Half-Split and Point-to-Point Methods

Point-to-point tracing starts at the power source and measures voltage at each terminal in sequence. When the reading drops from expected to zero (or near zero), the fault is between those two test points.

Half-split is faster on long ladders: measure at the midpoint of the circuit first. If voltage is present at midpoint, the fault is downstream; if absent, it is upstream. Keep splitting until you bracket the fault.

Always record every reading in your data table before moving to the next point. A table forces you to compare the reading to the specification and declare pass or fail at each point—not after the fact.

---

Common Faults and Their Meter Signatures

| Fault | What You Measure | Typical Reading |

|---|---|---|

| Open contact | Voltage across contact (with circuit energized) | Full supply voltage appears across the open |

| Shorted coil | Resistance across coil terminals (LOTO) | Near 0 Ω instead of rated coil resistance |

| Loose terminal | Voltage drop across terminal (loaded circuit) | >0.5 V drop where drop should be near 0 |

| Blown fuse | Voltage across fuse (circuit energized) | Full supply voltage across fuse |

| Incorrect voltage at terminal | Voltage at terminal vs. specification | Out-of-range reading; check transformer tap or upstream source |

Note: An open contact has full voltage across it because one side is connected to the source and the other side has no return path—the contact itself is blocking current, so all the voltage appears across the gap.

---

The 4–20 mA Analog Signal

Many sensors send process values as a 4–20 mA loop signal. To measure loop current, select DC milliamps on the DMM and break the loop to insert the meter in series—or clamp a DC-capable clamp meter around the single signal wire if available. A reading of 4 mA means the sensor sees minimum range; 20 mA means maximum range. A reading of 0 mA usually means a broken wire or unpowered transmitter.

---

Lab Procedure Summary

1. Review the circuit schematic and identify all numbered test points.

2. Predict the expected reading at each point using Ohm's law and the schematic.

3. Select meter function and range; verify meter operation on a known source.

4. For live measurements, don appropriate PPE; for resistance/continuity, apply LOTO.

5. Place leads, read the display, record in the data table, compare to specification, and record Pass or Fail.

6. After all readings, state your fault hypothesis with evidence from your table.

Key terms10

CAT IIIMeasurement Category III — the minimum safety rating required for DMMs and test leads used in industrial control panels and distribution circuits; it indicates the meter is designed to withstand transient overvoltages typical at that installation level.
Continuity testA meter function that passes a small current through a de-energized circuit path and beeps or displays low resistance when the path is complete; used to verify wiring connections and contact integrity with power removed.
Clamp meterA meter with a split-core current transformer jaw that clamps around a single conductor to measure AC or DC current without breaking the circuit.
Voltage dropThe reduction in voltage across a component or connection equal to the current through it multiplied by its resistance (V = IR); excessive drop across a terminal or contact indicates a fault.
Open circuit faultA break in the current path—such as an open contact, blown fuse, or broken wire—that causes full supply voltage to appear across the open point when measured with the circuit energized.
Shorted coilA relay or solenoid coil whose insulation has failed, creating a low-resistance path between windings; measured as near-zero ohms on a de-energized coil that should show its rated coil resistance.
4–20 mA loopA standard analog current signal used to transmit process values over a two-wire loop; 4 mA represents the minimum of the measured range and 20 mA represents the maximum, with 0 mA indicating a wiring or power fault.
Half-split methodA fault-isolation strategy that measures at the midpoint of a circuit first, then divides the remaining suspect portion in half repeatedly until the fault is bracketed between two test points.
Lockout/tagout (LOTO)The procedure required by OSHA 29 CFR 1910.147 to de-energize equipment, lock the energy-isolating device, and verify absence of energy before performing any work that requires power to be removed.
Signal tracingThe systematic measurement of voltage, current, or signal levels at successive test points in a circuit to locate the point where the expected value is absent or out of specification.

Worked examples4

1. A 120 VAC relay coil is rated at 800 Ω. What current should flow through it when fully energized, and what power does it consume?
  1. Use Ohm's Law: I = V ÷ R = 120 V ÷ 800 Ω
  2. I = 0.15 A (150 mA)
  3. Use power formula: P = V × I = 120 V × 0.15 A
  4. P = 18 W
Answer: The coil draws 0.15 A and consumes 18 W. If your clamp meter reads significantly less current, suspect a partially open circuit; if it reads more, suspect a shorted turn reducing coil resistance.
2. Two 24 VDC indicator lamps are wired in parallel across a PLC output. Lamp A draws 80 mA and Lamp B draws 120 mA. What is the total current the output card must supply, and what is the resistance of each lamp?
  1. In a parallel circuit, total current = sum of branch currents: I_total = 80 mA + 120 mA = 200 mA
  2. Resistance of Lamp A: R_A = V ÷ I = 24 V ÷ 0.080 A = 300 Ω
  3. Resistance of Lamp B: R_B = V ÷ I = 24 V ÷ 0.120 A = 200 Ω
  4. Verify with clamp meter: clamping around the common supply wire should show 200 mA total.
Answer: Total current is 200 mA. Lamp A resistance is 300 Ω; Lamp B resistance is 200 Ω. A clamp-meter reading near 200 mA on the supply conductor confirms both lamps are drawing correctly.
3. A 4–20 mA pressure transmitter has a range of 0–200 PSI. The PLC analog input reads a loop current of 12 mA. What pressure does this represent?
  1. The 4–20 mA span represents 16 mA total (20 − 4 = 16 mA) corresponding to 200 PSI.
  2. Scale factor: 200 PSI ÷ 16 mA = 12.5 PSI per mA
  3. Current above the 4 mA live-zero: 12 mA − 4 mA = 8 mA above zero
  4. Pressure = 8 mA × 12.5 PSI/mA = 100 PSI
Answer: A 12 mA reading represents 100 PSI, exactly midscale. If the transmitter is measuring a known 100 PSI source and your loop current reads 12 mA, the transmitter is functioning correctly.
4. A technician measures 4.7 V across a wire terminal in a 24 VDC circuit while 0.2 A flows through it. Is this terminal within specification, and what does the reading indicate?
  1. Calculate the resistance implied by the reading: R = V ÷ I = 4.7 V ÷ 0.2 A = 23.5 Ω
  2. A properly torqued terminal connection should have near-zero resistance and a voltage drop well under 0.5 V at this current (0.2 A × <0.025 Ω = <5 mV).
  3. A 4.7 V drop at only 0.2 A means an effective resistance of 23.5 Ω — far above normal for a terminal connection.
  4. This indicates a loose, corroded, or damaged terminal that is consuming 4.7 V × 0.2 A = 0.94 W and starving the downstream load of voltage.
Answer: The terminal is out of specification. A 4.7 V drop is far above the acceptable near-zero drop and indicates a loose or corroded connection. The terminal should be tightened or replaced, with power locked out first per OSHA 29 CFR 1910.147.

The math in this lesson2

Learners scale a 12 mA loop current to a 0–200 PSI pressure.
F-LE.1A-CED.4
Brush up in the math halls at newSchoolWorks.com:
In class: Review Ohm's law (V = IR), power formula (P = VI), and series/parallel circuit rules; students solve six numerical problems involving control-circuit voltages and expected current draw, using calculators. · Instructor demonstrates meter lead placement for voltage measurement across a coil, current measurement on a load leg with a clamp meter, and resistance check of a limit-switch contact with power removed; students sketch the measurement setup for each. · Paired lab: instructor introduces five seeded faults (open contact, shorted coil, loose terminal, blown fuse, incorrect voltage at terminal) one at a time; each pair measures, records readings in a data table, and states whether the component is within specification before moving to the next fault.
Materials: PLC control-panel training station, CAT III digital multimeters (one per pair), clamp meters, test leads, 120 VAC and 24 VDC power supplies, fault-insertion board, data-recording worksheet, PMMI Industrial Electricity 1 reference
Check: Lab data table reviewed by instructor: student must record correct measurement at every test point (within stated meter tolerance) and give a correct pass/fail interpretation for at least 8 of 10 measurements; 80% pass.

Practice check8

Answer each question, then check it. Nothing is recorded; this is your own practice.

PMMI Industrial Electricity 1 — Circuit Troubleshooting
1. A technician measures full 120 VAC supply voltage across a fuse in an energized control circuit. What does this reading most likely indicate?
PMMI Industrial Electricity 1 — Safety
2. Which OSHA standard specifically requires lockout/tagout procedures before performing a resistance check on a de-energized relay coil?
PMMI Industrial Electricity 2 — I/O Signal Diagnosis
3. A 24 VDC PLC input circuit has a sensor output stuck at approximately 12 VDC instead of 0 VDC or 24 VDC. What is the most likely cause of this mid-range reading?
PMMI Industrial Electricity 1 — Measurement Technique
4. When using a clamp meter to measure current on a 24 VDC circuit, which of the following procedures is correct?
PMMI Industrial Electricity 1 — Component Testing
5. A relay coil is rated at 500 Ω. After locking out the panel, a technician measures 2 Ω across the coil terminals. What fault does this indicate?
PMMI Industrial Electricity 1 — Ohm's Law
6. Using Ohm's Law, what current flows through a 240 Ω control-circuit resistor connected across a 24 VDC supply?
PMMI Industrial Electricity 2 — Analog Signals
7. A 4–20 mA temperature transmitter has a range of 0–400 °F. The loop current measures 8 mA. What temperature is being sensed?
PMMI Industrial Electricity 1 — Electrical Safety / NFPA 70E
8. According to NFPA 70E, before touching terminals in an energized 120 VAC control panel, a technician must: