Objective. Students will explain the operating principle of a doubly-fed induction generator (DFIG) or permanent-magnet generator (PMG) commonly used in utility-scale turbines and identify the major electrical components in the generator circuit.
This lesson, its worked examples and its practice questions has not yet been verified by a licensed professional engineer or master tradesperson or by a certification or approval body. It is a study draft and may contain errors. Do not use it as instructions for work on a job site or on live equipment. Always follow your instructor, your supervising professional, and current official references and regulations.
VoTechWorks program approval and accreditation are still in progress. Credentials are issued only by the certifying bodies named in each program, after their own exams.
A wind turbine converts the kinetic energy of moving air into mechanical rotation at the main shaft, then converts that rotation into three-phase alternating current (AC) electricity delivered to the grid. The component that performs the second conversion is the generator. Understanding how the generator works—and how power electronics support it—is essential for every wind turbine technician.
Wind speed is never constant. Early turbines ran at fixed rotor speed, which meant the generator always spun at the same rate regardless of wind conditions. This wasted energy when wind was slow and stressed components when wind was gusty. Modern utility-scale turbines use variable-speed operation: the rotor turns faster or slower as wind changes, and power electronics convert the resulting variable-frequency electrical output into the steady 60 Hz AC required by the North American grid. Two generator types dominate the industry today: the doubly-fed induction generator (DFIG) and the permanent-magnet generator (PMG).
A DFIG is a wound-rotor induction machine. It has two sets of windings that both carry real power—hence the name doubly fed.
Stator: The stator is the stationary outer assembly of the generator. Its three-phase windings connect directly to the medium-voltage transformer and, through it, to the grid. The stator delivers the majority of the turbine's output power—typically around 70 percent or more—directly as AC at grid frequency.
Rotor and slip rings: The rotor is the rotating inner assembly, also wound with three-phase coils. Unlike a squirrel-cage motor, the DFIG rotor windings are brought out through slip rings—conductive rings mounted on the rotor shaft that allow a stationary brush assembly to make electrical contact with the spinning rotor. This is how power and control signals pass between the stationary converter and the rotating rotor.
Rotor-side converter (RSC): The RSC is a power-electronic converter (typically an IGBT-based inverter) connected between the slip rings and a DC link. By controlling the frequency and magnitude of voltage injected into the rotor, the RSC regulates generator torque, reactive power, and speed over a range typically spanning roughly ±30 percent of synchronous speed. When the rotor spins faster than synchronous speed, power flows from the rotor through the RSC to the grid; below synchronous speed, power flows the other direction.
DC link: The RSC and the grid-side converter share a common DC bus—capacitor banks that hold a stable DC voltage between the two converters.
Grid-side converter (GSC): The GSC converts the DC link voltage back to AC at exactly grid frequency and voltage, delivering the rotor's share of power to the grid. The GSC also manages reactive power and maintains the DC link voltage.
Transformer and grid connection: Both the stator output and the GSC output combine at a turbine transformer (pad-mount or tower-base unit) that steps voltage up to the wind farm collection voltage before feeding the grid.
A PMG uses powerful rare-earth magnets mounted on the rotor instead of wound coils. Because the magnets create the rotor's magnetic field without any external electrical supply, there are no slip rings. PMGs are often used in direct-drive turbines (no gearbox) or with a single-stage gearbox.
Since the rotor speed—and therefore the output frequency—varies continuously with wind speed, the PMG's AC output cannot connect directly to the grid. Instead:
1. A full-power rectifier (diode bridge or active front-end converter) converts the variable-frequency AC from the stator into DC.
2. The DC feeds a grid-side inverter that produces 60 Hz AC at the correct voltage for the transformer.
Because all of the generator's power flows through the power electronics, the converter rating must equal the turbine's full nameplate power—unlike a DFIG where the converter handles only a fraction. This makes the PMG converter larger but eliminates the slip rings, reducing brush maintenance.
| Component | DFIG | PMG |
|---|---|---|
| Stator windings | Three-phase wound | Three-phase wound |
| Rotor | Three-phase wound + slip rings | Permanent magnets, no slip rings |
| Rotor-side converter (RSC) | Present (partial power) | Not applicable |
| Full-power rectifier | Not applicable | Present |
| DC link | Present | Present |
| Grid-side converter (GSC) | Present (partial power) | Present (full power) |
| Step-up transformer | Present | Present |
Generator circuits include overcurrent protection (fuses and circuit breakers), ground-fault monitoring, insulation-resistance monitoring, thermal sensors in the windings (thermistors or RTDs), and overspeed protection. The converter cabinet contains additional fuses, contactors, and control boards that monitor DC link voltage, current limits, and fault conditions. Crowbar circuits in some DFIGs protect the rotor converter from voltage spikes during grid faults.
Generator and converter cabinets contain hazardous voltage. DC link capacitors can remain charged to dangerous voltages even after the turbine is shut down—always follow the manufacturer's discharge verification procedure before opening any cabinet. Apply full lockout/tagout (LOTO) to the main electrical disconnect and confirm with a calibrated voltage tester before touching any conductors. Wear arc-flash rated PPE appropriate to the incident energy level established in the site's arc-flash hazard analysis. Never defeat or bypass thermal or overcurrent protection devices. Slip ring and brush inspection may be performed only with proper LOTO in place.